User manual

Detaileddescriptionsoftheeld-buscoupler| Modbus TCP eld-bus coupler UR20-FBC-MOD-TCP
56 1432790000/03/02.2014Manual u-remote
OverviewoftheeditableparametersUR20-FBC-MOD-TCP
Parameter Optional values Default value
IP-Address Input of 4 numbers between 0-255 192.168.0.222
Subnet mask Input of 4 numbers between 0-255 255.255.255.0
Gateway Input of 4 numbers between 0-255 192.168.0.1
IP Conguration Static, DHCP, BootP Static
IP-Address USB-Port 192.168.1.202; 192.168.2.202, 192.168.3.202, 192.168.4.202,
192.168.5.202
192.168.1.202
Webserver via Ethernet disabled / enabled disabled
Save conguration no / yes / Standard no, seeeld-bus register 0x113E-0x113F
Status Modbus watchdog Watchdog time in steps of 10ms 0 *10ms, seeeld-bus register 0x1120
Modbus Connection Timeout Connection watchdog time in sec 1s, seeeld-bus register 0x1031
ModbusConnectionMode write for all, 1stWr1stServe, 1stConn1stServe write for all, seeeld-bus register 0x1130
RefListMode disabled / enabled deaktiviert, seeeld-bus register 0x1132
Process alarm disabled / enabled seeeld-bus register 0x1133
Diagnostic alarm disabled / enabled seeeld-bus register 0x1134
Behaviour of outputs on eld-bus error All outputs off / Enable substitute values / Hold last value All outputs off, seeeld-bus register 0x1135
Module behaviour on hot swap Continue data exchange / Behaviour like eld-bus error Continue data exchange, seeeld-bus register
0x1136
Data format Motorola / Intel Motorola, seeeld-bus register 0x1137