Detailed descriptions of I/O modules | Digital counter module UR20-1CNT-100-1DO
134 1432790000/03/02.2014Manual u-remote
TechnicaldataUR20-1CNT-100-1DO(OrderNo.1315570000)
General data
Weight
83 g
ATEX
Approval for operation in potentially explosive atmosphere Zone 2 pending
Foradditionalgeneraldata,seeSection3.4
Overview of the editable parameter UR20-1CNT-100-1DO
Channel Description Options(Value) Default value
Diagnostic alarm disabled (0) / enabled (1) disabled
0 Filter time signal A 0,01 ms [100kHz] (0) / 0,017 ms [50kHz] (1) / 0,033 ms [30kHz] (2) / 0,1 ms
[10kHz] (3) / 0,2 ms [5kHz] (4) / 0,5 ms [2kHz] (5) / 1 ms [1kHz] (6)
0,01 ms
0 Filter time signal B 0,01 ms [100kHz] (0) / 0,017 ms [50kHz] (1) / 0,033 ms [30kHz] (2) / 0,1 ms
[10kHz] (3) / 0,2 ms [5kHz] (4) / 0,5 ms [2kHz] (5) / 1 ms [1kHz] (6)
0,01 ms
0 Filter time latch 0,01 ms (0) / 0,017 ms (1) / 0,033 ms (2) / 0,1 ms (3) / 0,2 ms (4) / 0,5 ms (5) /
1 ms (6)
0,01 ms
0 Filter time gate 0,01 ms (0) / 0,017 ms (1) / 0,033 ms (2) / 0,1 ms (3) / 0,2 ms (4) / 0,5 ms (5) /
1 ms (6)
0,01 ms
0 Filter time reset 0,01 ms (0) / 0,017 ms (1) / 0,033 ms (2) / 0,1 ms (3) / 0,2 ms (4) / 0,5 ms (5) /
1 ms (6)
0,01 ms
0 Process alarm HW gate open disabled (0) / enabled (1) disabled
0 Process alarm HW gate closed disabled (0) / enabled (1) disabled
0 Process alarm overow disabled (0) / enabled (1) disabled
0 Process alarm underow disabled (0) / enabled (1) disabled
0 Process alarm comp. value disabled (0) / enabled (1) disabled
0 Process alarm end value disabled (0) / enabled (1) disabled
0 Process alarm latch value disabled (0) / enabled (1) disabled
0 Counting mode count endless (0) / once - forward (1) / once - backwards (2) / once - no main
direction (3) / periodic - forward (4) / periodic - backwards (5) / periodic - no main
direction (6)
count endless
0 Condition for DO disabled (0) / higher equal comparison value (1) / lower equal comparison value (2)/
equal comparison value (3)
disabled
0 Counter dir. signal B inv. disabled (0) / enabled (1) disabled
0 Reset disabled (0) / high level (1) / rising edge 0-1 (2)/
rising edge once 0-1 (3)
0 Signal mode Rotary transducer - single (0) / Rotary transducer - double (1) / Rotary transducer -
quadruple (2) / Pulse and Direction (3) / disabled (4)
disabled
0 HW gate disabled (0) / enabled (1) disabled
0 Counter behaviour internal gate Interrupt counting (0) / Cancel counting (1) interrupt counting
0 End value -2147483648 ... 2147483647 2147483647
0 Load value -2147483648 ... 2147483647 0
0 Hysteresis 0 ... 255 0
0 Pulse duration 0 ... 255 [Input value x 2 = output time; corresponds to 0 ... 510ms] 0