User manual

Detailed descriptions of I/O modules | Analogue output module UR20-4AO-UI-16
196 1432790000/03/02.2014Manual u-remote
MeasurementrangeUR20-4AO-UI-16
Measurementrange Voltage(U) Decimal(D) Hexadecimal Range Conversion
±10V
Siemens S5-format
11,76V 19268 0x4B44 Overloading
D= 16384 x U / 10
U=D x 10 / 16384
10V 16384 0x4000
Nominal range
5V 8192 0x2000
0V 0 0x0000
-5V -8192 0xE000
-10V -16384 0xC000
-11,76V -19268 0xB4BC Underloading
2 … 10V
Siemens S7-format
11,41V 32511 0x7EFF Overloading
D= 27648 x (U – 2) / 8
U=D x 8 / 27648 + 2
10V 27648 0x6C00
Nominal range6V 13824 0x3600
2V 0 0x0000
0,59V -4864 0xED00 Underloading
2 … 10V
Siemens S5-format
11,41V 19268 0x4B44 Overloading
D= 16384 x (U – 2) / 8
U=D x 8 / 16384 + 2
10V 16384 0x4000
Nominal range6V 8192 0x2000
2V 0 0x0000
0,40V -3277 0xF333 Underloading
1 … 5V
Siemens S7-format
5,7V 32511 0x7EFF Overloading
D= 27648 x (U – 1) / 4
U=D x 4 / 27648 + 1
5V 27648 0x6C00
Nominal range3V 13824 0x3600
1V 0 0x0000
0,30V -4864 0xED00 Underloading
1 … 5 V
Siemens S5-format
5,7V 19268 0x4B44 Overloading
D= 16384 x (U – 1) / 4
U=D x 4 / 16384 + 1
5V 16384 0x4000
Nominal range3V 8192 0x2000
1 V 0 0x0000
0,20V -3277 0xF333 Underloading
0  … 5V
Siemens S7-format
5,88V 32511 0x7EFF Overloading
D= 27648 x U / 5
U=D x 5 / 27648
5V 27648 0x6C00
Nominal range2,5V 13824 0x3600
0V 0 0x0000
0 … 5V
Siemens S5-format
5,88V 19268 0x4B44 Overloading
D= 16384 x U / 5
U=D x 5 / 16384
5V 16384 0x4000
Nominal range2,5V 8192 0x2000
0V 0 0x0000