User manual

Detailed descriptions of I/O modules | Analogue input module UR20-4AI-TC-DIAG
211Manual u-remote1432790000/03/02.2014
VoltagemeasurementrangesUR20-4AI-TC-DIAG
Measurementrange
Voltage Decimalsignalrange Hexadecimalsignalrange
±15.625mV
15.625mV 32767 0x7FFF
-15.625mV -32768 0x8000
±31.25mV
31.25mV 32767 0x7FFF
-31.25mV -32768 0x8000
±62.5mV
62.5mV 32767 0x7FFF
-62.5mV -32768 0x8000
±125mV
125mV 32767 0x7FFF
-125mV -32768 0x8000
±250mV
250mV 32767 0x7FFF
-250mV -32768 0x8000
±500mV
500mV 32767 0x7FFF
-500mV -32768 0x8000
±1V
+1V 32767 0x7FFF
-1V -32768 0x8000
±2V
+2V 32767 0x7FFF
-2V -32768 0x8000