User manual

Detaileddescriptionsoftheeld-buscoupler| Modbus TCP eld-bus coupler UR20-FBC-MOD-TCP
66 1432790000/03/02.2014Manual u-remote
0x2A00 – 0x2A7FCurrentmodulelist
Each module identier is made up of 4 bytes (2 registers)
(see the Overview of module IDs). The modules that were
connected when the coupler was started are entered here.
To simplify conguration, the current module list can be cop-
ied into the reference module list.
0x8000 – 0x87FFProcessdatainputs
For each module a data length of 64 Byte (32 Register) is
reserved.
Example: Module 3 starts at address 0x8040.
0x9000 – 0x97FFProcessdataoutputs
For each module a data length of 64 Byte (32 Register) is
reserved.
Example: Module 3 starts at address 0x9040.
0xA000 – 0xA7FFDiagnostics
For each module a diagnostics data length of 64 Byte (32
Register) is reserved.
Example: Module 3 starts at address 0xA040.
In case of a diagnostics message, the 47 bytes of the mod-
ule diagnosis are entered here from the corresponding tables
(see the table of diagnostic data in the corresponding mod-
ule description in the Module chapter).
If a 1 is set in register 0x1134, reading out the correspond-
ing diagnosis results in a conrmation of the alarm.
0xB000 – 0xB7FFProzessalarms
For each module a process alarm data length of 64 Byte (32
Register) is reserved.
Example: Module 3 starts at address 0xB040.
In case of a process alarm, the 4 bytes of the module are
entered here from the corresponding table (see the table of
process alarms in the corresponding module description in
the Module chapter).
0xC000 –0xC7FFParameters
For each module a parameter data length of 64 Byte
(32Register) is reserved.
Example: Module 3 starts at address 0xC040.
To parameterise a module, use the web server (see the Web
Server chapter). After parameterisation, you can read out the
parameter set for the corresponding module using the mod-
bus command function code 3 Read Holding Registers You
can copy this data into your project.