User manual

Replacingcomponents | Removing/replacing cables
279Manual u-remote1432790000/03/02.2014
11.5 Removing/replacingcables
WARNING
Explosion risk!
Prior to starting work, make sure that
there is not a potentially explosive atmos-
phere!
WARNING
Operation of the machine/system can
be disrupted!
If the machine/system is put into a dan-
gerous state as a result of the removal of
cables a replacement can only be made
once the machine/system is disconnected
from thepower!
WARNING
Dangerous contact voltage!
Prior to removing modules, the u-remote
station must be completely de-energised
(supply of the field bus coupler and all
external feed-in).
Make sure that the place of installation
(switch cabinet etc.) has been discon-
nected from the power supply.
ATTENTION
The product can be destroyed by elec-
trostatic discharge!
The components in the u-remote series can
be destroyed by electrostatic discharge.
Please make sure that personnel and work
equipment are adequately earthed!
Using a 3-mm screwdriver, push in the pusher adjacent to
the cable to be removed and pull the wire out.
Pushingthepusherinwithascrewdriver
Release the pusher.
Insert the new wire into the opening. To do so, you do
not need to push in the pusher.