User manual

Conguration | Parameter overview
27Manual u-remote1432790000/03/02.2014
4.9 Parameteroverview
Overview of the editable parameters
Product Order No. Parameter Optional values Default value
UR20-FBC-PB-DP
1334870000 DP-Alarm mode V0 / V1 V1
DP alarm mode V0 FormodeV0,thealarmtriggersaresetintheparameterdata.
Diagnostic alarm* enabled / disabled disabled
Process alarm* enabled / disabled disabled
Hot-plug alarm* enabled / disabled enabled
*These switches are always selectable, but they only have a function in mode V0. Diagnostic messages are generated which are
not acknowledged by the PLC.
DP alarm mode V1 InmodeV1,thealarmtriggersaresetintheengineeringenvironment.
Diagnostic alarm** enabled / disabled disabled
Process alarm** enabled / disabled disabled
Hot-plug alarm** enabled / disabled enabled
**These switches can be selected only in mode V1, in V0 they are inactive. Diagnostic messages are generated which are
acknowledged by the PLC.
Identier-related diagnosis*** enabled / disabled enabled
Channel-related diagnosis*** enabled / disabled enabled
Module status*** enabled / disabled enabled
***A diagnostic block is attached to the diagnostic message.
Data format Motorola / Intel Motorola
Field-bus error output behaviour All outputs off / activate replacement
values / retain last value
All outputs off
Module behaviour during hot swap Continue data exchange /
behaviour as with eld-bus error
Continue data exchange
UR20-FBC-PN-IRT
1334880000 Process alarm disabled / enabled disabled
Diagnostic alarm disabled / enabled disabled
Type of diagnostic Extended channel diagnostic (short
diagnostic)
Manufacturer-specic diagnostic (com-
plete diagnostic)
Extended channel diagnostic (short
diagnostic)
Behaviour of outputs on eld-bus errors All outputs off / Enable substitute value /
Hold last value
All outputs off
Module behaviour on hot swap Continue data exchange / Behaviour like
eld-bus error
Continue data exchange
Data format Motorola / Intel Motorola
Webserver via Ethernet disabled / enabled disabled