Detaileddescriptionsoftheeld-buscoupler | Modbus TCP eld-bus coupler UR20-FBC-MOD-TCP
55Manual u-remote1432790000/03/02.2014
TechnicaldataUR20-FBC-MOD-TCP(OrderNo.1334930000)
System data
Connection
2 x RJ-45
Field-bus protocol
Modbus TCP
Processimage
Process data max. 8kBytes
Parameter data max. 1024kBytes
Diagnostic data max. 1024kBytes
Number of modules
max. 64 active
Configurationinterface
USB 2.0
Transfer rate
Field-bus 10Mbps/100Mbps
u-remote system bus Max. 48Mbps
Supply
Supplyvoltageforsystemandinputs
24VDC +20 % / -15 %
Supplyvoltageforoutputs
24VDC +20 % / -15 %
Max. feed-in current for input modules
10A
Max. feed-in current for output modules
10A
Currentconsumption(internal),typ.
112mA
Connection data
Type of connection
“PUSH IN”
Line connection cross-section
Single-wired 0.14 – 1.5mm
2
(AWG 16 – 26)
Fine-wired 0.14 – 1.5mm
2
(AWG 16 – 26)
General data, see Section 3.2
AddressingusingDHCPmode
The web server can be used to dene whether a static IP ad-
dress should be used (default) or if the address is automati-
cally assigned (DHCP/BootP). In case of an automatically
assigned address, the DHCP server assigns an IP address to
the client. This can be read using the web server.