Detaileddescriptionsoftheeld-buscoupler | Modbus TCP eld-bus coupler UR20-FBC-MOD-TCP
63Manual u-remote1432790000/03/02.2014
0x1018 – 0x101BCollectivediagnosticsmessageforI/O
modules
If a diagnostic alarm is activated (Register 0x1134) and there
is a diagnostic message for a module, it is indicated here
with a set bit. A module’s slot position corresponds to its
position in the 64-bit data eld (minus passive modules with-
out slot recognition). Example: 0x0000 0000 0000 0002 =
There is a diagnostic alarm for module 2.
Reading the module’s diagnostic memory (0xAXXX) con-
rms the diagnosis and resets the corresponding bit. In
case of multiple diagnoses for one module, only the most
up-to-date diagnosis is displayed. The next diagnostic is then
placed in a wait loop and only becomes active once the cur-
rent one has been conrmed.
0x101C – 0x101FCollectiveprocessalarmmessageforthe
I/O modules
If a process alarm is activated (Register 0x1133) and there
is an alarm for a module, this is indicated here with a set bit.
A module’s slot position corresponds to its position in the
64-bit data eld (minus passive modules without slot rec-
ognition). Example: 0x0000 0000 0000 0002 = These is a
process alarm for module 2.
Reading the module’s process alarm memory (0xBXXX)
conrms the alarm and resets the corresponding bit. In case
of multiple process alarms for one module, only the latest
alarm is displayed. The next alarm is then placed in a wait
loop and only becomes active once the current one has been
conrmed.
0x1028 – 0x102FModulestatus
The module status (2 bits per module) is displayed in the cor-
responding bit positions of the 128 bits.
00 Valid data from this module
01 Invalid data, faulty module
10 Invalid data, incorrect module
11 Invalid data, missing module
0x1030MODBUSDATAEXCHANGEwatchdog,current
time
Amount of time (input value x 10ms) still remaining on the
active watchdog to monitor the exchange of process data.
If a 0 is read, the watchdog has expired and must be re-
started.
If 0xFFFF is read, the watchdog is deactivated.
0x1120MODBUSDATAEXCHANGEwatchdog,predened
time
In this register, the watchdog is activated/deactivated and
the watchdog time is set. An input can be made as long as
the watchdog is deactivated or it is activated and still run-
ning. But it is accepted only after a watchdog reset to the
current time. The length is calculated with the input value x
10ms. Entering 0 deactivates the watchdog.
0x1121MODBUSDATAEXCHANGEWatchdog
ResetRegister
If Bit 0 in this register is set, the predened time is loaded
into the watchdog time (watchdog reset).
If Bit 8 in this register is set, an expired watchdog (value 0 in
register 1030) is reactivated.