User manual

System overview | General technical data for the eld-bus coupler
11Manual u-remote1432790000/03/02.2014
3.2 Generaltechnicaldatafortheeld-buscoupler
Type of connection
“PUSH IN”
Line connection cross-section
Single-wired 0.14 – 1.5mm
2
(AWG 16 – 26)
Fine-wired 0.14 – 1.5mm
2
(AWG 16 – 26)
Dimensions
Height 120,0mm / 4.72"
(with release lever: 128,0mm / 5,04")
Width
52,0mm / 2.05"
Depth
76,0mm / 2.99"
Weight
220g
Protectionclass(DINEN60529)
IP 20
FlammabilityratingUL94
V-0
Temperature data
Operation (horizontal installation) -20°C to +60°C / - 4 ... +140°F (8-A power supply)
-20°C to +55°C / - 4 ... +131°F (10-A power supply)
Operation (vertical installation) -20°C to +55°C / - 4 ... +131°F (6-A power supply)
-20°C to +50°C / - 4 ... +122°F (8-A power supply)
Storage, transport -40°C to +85°C / - 40 ... +185°F
Humidity
Operation 95 %, non-condensing as per DIN EN 61131-2
Storage, transport 95 %, non-condensing as per DIN EN 61131-2
Air pressure
Operation ≥ 795 hPa (altitude ≤ 2000m)
as per DINEN61131-2
Storage, transport ≥ 700 hPa (altitude ≤ 3000m)
as per DINEN61131-2
Vibration resistance
5Hz ≤ f ≤ 8.4Hz: 3.5mm amplitude as per IEC 60068-2-6
8.4Hz ≤ f ≤ 150Hz: 1 g acceleration as per IEC 60068-2-6
Shock resistance
15 g over 11ms, half sinewave, as per IEC 60068-2-27
Potentialisolation
Test voltage 500V DC eld/system
Pollution severity level 2
Overvoltage category II
Approvals
cULus UL 508
Potentially explosive atmosphere Zone 2* ATEX Directive 94/9/EC
Standards
EMC EN 61000 (partial standards as per the requirements of EN 61131-2)
Explosion protection EN 60079-0:2009 and EN60079-15:2010
PLC DINEN61131-2
All product-specic technical data is available in the corresponding product description in Chapter5.