Detailed descriptions of I/O modules | Analogue input module UR20-4AI-TC-DIAG
210 1432790000/03/02.2014Manual u-remote
DiagnosticdataUR20-4AI-TC-DIAG
Name Bytes Bit Description Default
Error indicator 0
0 Module error
1 Internal error
2 External error
3 Channel error
4 Reserved 0
5 Power supply fault
6 Reserved 0
7 Parameter error
Module types 1
0
Module type 0x05
1
2
3
4 Channel information available 1
5 Reserved 0
6 Reserved 0
7 Reserved 0
Error byte 2 2 0 – 7 Reserved 0
Error byte 3 3
0 – 2 Reserved 0
3 Internal diagnostic FIFO full
4 Power supply fault
5 Reserved 0
6 Process alarm lost
7 Reserved 0
Channel type 4
0 – 6 Channel type 0x71
7 Reserved 0
Diagnostic bits
per channel
5
Number of diagnostic bit per
channel
8
Number of
channels
6
Number of similar channels per
module
4
Channel error 7
0 Error at channel 0
1 Error at channel 1
2 Error at channel 2
3 Error at channel 3
4 – 7 Reserved 0
Channel error 8 8 – 15 Reserved 0
Channel error 9 16 – 23 Reserved 0
Channel error 10 24 – 31 Reserved 0
Channel 0 error 11
0 Parameter error
1 Reserved 0
2 Reserved 0
3 CJC error
4 Line break
5 Process alarm lost
6 Lower limit exceeded
7 Upper limit exceeded
DiagnosticdataUR20-4AI-TC-DIAG
Name Bytes Bit Description Default
Channel 1 error 12
0 Parameter error
1 Reserved 0
2 Reserved 0
3 CJC error
4 Line break
5 Process alarm lost
6 Lower limit exceeded
7 Upper limit exceeded
Channel 2 error 13
0 Parameter error
1 Reserved 0
2 Reserved 0
3 CJC error
4 Line break
5 Process alarm lost
6 Lower limit exceeded
7 Upper limit exceeded
Error in chan-
nel 3
14
0 Parameter error
1 Reserved 0
2 Reserved 0
3 CJC error
4 Line break
5 Process alarm lost
6 Lower limit exceeded
7 Upper limit exceeded
Channel 4 error
to
Channel 31
error
15 – 42 0 – 7 Reserved 0
Time stamp 43 – 46 Time stamp [µs] (32bit)