Data Sheet
Datenblatt
Surge protection
VPU III R 230V/6KV AC
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technische Daten
Erstellungs-Datum December 20, 2013 8:37:39 AM CET
Katalogstand xx.xx.xxxx / Technische Änderungen vorbehalten 2
Dimensions and weights
Width 18 mm
Height 102 mm
Depth 71.5 mm
Net weight 68 g
Temperatures
Operating temperature -40 °C...+70 °C
Storage temperature -40 °C...+80 °C
General data
Acoustic signal No
Colour Red
Design Installation housing; 1TE,
Insta IP 20
Lightning arrester
Yes
Mounting rail
TS 35, TS 35 x 15, TS 35
x 7.5
Optical function display Green LED = OK, Red LED
= arrester is defective,
replace
Protection degree IP 20
Segment
Power distribution
UL 94 flammability rating V-0
Insulation coordination acc. to EN 50178
Pollution severity 2
Surge voltage category II
Interference voltage
On output side (L - N) at max. discharge
current; smaller 1,200 V
On output side (L /N - PE) at max.
discharge current; smaller 1,800 V
technical data
Rated voltage (AC) 230 V
Rated current 16 A
Max. continuous voltage, Uc (AC)
300 V
Operating current, I
max.
16 A
Highest continuous voltage (AC)
275 V
Temporary surge voltage (over-voltage) -
TOV 438 V
Combined pulse U
OC
6 kV
Fuse, max.
16 A
Short-circuit current rating I
SCCR
1.5 kA
Discharge current, nominal,per path,
(8/20 µs) 3 kA
Discharge current, max. (8/20 µs)
3 kA
Protection level U
P
(typ.)
≤ 1.8 kV
Leakage current at U
n
30 µA
Signalling contact
250 V 1 A 1 NC
Standards IEC61643-11,
EN61643-11
Colour
Red
Requirements class, acc. to EN
61643-11 T3
Requirements category acc. to IEC
61643-11 Type III
Response time < 100 ns
Mains frequency at 250 Vmax 50...60 Hz
Technical data, signal line
Rated current I
N