Information
connectPower PROeco
Derating curves
–25 0 20 30 40 50 60 70
120
100
80
60
40
20
0
Ambient temperature (°C)
≤ 480 Watt
I
output
(% I
N
)
–25 0 20 30 40 50 60 70
120
100
80
60
40
20
0
Ambient temperature (°C)
960 Watt
I
output
(% I
N
)
PROeco power supplies with basic functionality
and a high level of reliability
•
Single- and three-phase switched-mode power supply units
• Slim design
• Large temperature range from –25 °C to 70 °C
• The output voltage can be precisely adjusted via the
potentiometer on the front
• Remote monitoring via integrated status relay
• Three-coloured LED indicators for simple error detection
• Advanced visual warning at 90 % rated output current
• International approvals
Technical data
General technical data
Efciency
Earth discharge current
Ambient temp. operating / storage temperature
Max. perm. air humidity (operation)
Degree of protection
Class of protection
Pollution degree
Insulation voltage input/output
MTBF
Parallel connection option
Housing version
Mounting position, installation notice
Short-circuit protection
Overload protection
Overtemperature protection
Input
AC frequency range
Input fuse (internal)
Output
Ramp-up time / residual ripple, switching peaks
Capacity load
Signalling
DC OK
Alarm
Error
Voltage monitoring / no-voltage contact / contact load
Relay on / off
EMC / shock / vibration
Noise emission acc. to EN55022
Noise immunity tests acc. to
Limiting of mains voltage harmonic currents
Resistance against vibration and shock
Electrical safety (applied standards)
Electrical equipment of machines
Safety transformers for switched-mode power units
Machinery with electronic equipment
Safety extra-low voltage
Protective separation / protection against electrical shock
Protection against dangerous shock currents
up to 93 %
< 1 mA
–25 °C…+70 °C / –40 °C… +85 °C
5 %…95 % RH
IP20
I, with PE connection
2
3 kV I/O / 2 kV E/earth / 0,5 kV A/earth
> 500.000 h acc. to IEC 1709 (SN29500)
Yes, max. 5 without diode module
Metal, corrosion resistant
Horizontal on mounting rail TS35, 50 mm spacing
top and bottom for free air circulation
Yes, automatic restart
Yes, IU characteristic curve
Yes, automatic restart
47 … 63 Hz
Yes
< 100 ms / < 50 mVSS @ 24 V DC, I
N
Unrestricted
LED green (U
output
>90% U
N
)
LED yellow (I
output
> 90 % I
N
)
LED red (Overload, overtemperature, short-circuit, U
output
< 20.4 V DC)
Yes / NO contact / max. 30 V AC/DC 1 A
Output voltage > 21.6 V DC / < 20.4 V DC
Class B
EN61000-4-2 (ESD), EN61000-4-3 and EN61000-4-8 (Fields),
EN61000-4-4 (Burst), EN61000-4-5 (Surge),
EN61000-4-6 (conducted), EN61000-4-11 (Dips)
Acc. to EN61000-3-2
1 g acc. to EN50178, shock: 15 g in all directions
Acc. to EN60204
Acc. to EN61558-2-17
Acc. to EN50178 / VDE0160
SELV acc. to EN60950-1, PELV acc. to EN60204-1
VDE0100-410 / acc. to DIN57100-410
Acc. to VDE0106-101
6