Data Sheet

Data sheet
MICROSERIES
MAS DC/DC select
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date May 27, 2019 3:20:36 PM CEST
Catalogue status 23.05.2019 / We reserve the right to make technical changes. 2
Dimensions and weights
Length 88 mm
Length (inches) 3.465 inch
Width 6.1 mm
Width (inches) 0.24 inch
Depth 97.8 mm
Depth (inches)
3.85 inch
Net weight 52 g
Temperatures
Operating temperature, max. 55 °C
Operating temperature, min. 0 °C
Storage temperature, max. 85 °C
Storage temperature, min. -20 °C
Operating temperature 0 °C...55 °C
Storage temperature -20 °C...85 °C
Probability of failure
MTTF 440 Years
Environmental Product Compliance
REACH SVHC Lead 7439-92-1
Rated data UL
Certificate No. (cURus) E175400
Input
Number of inputs 1
Input voltage 0...10 V
Input resistance, voltage 100 kΩ
Input current 0...20 mA, 4...20 mA
Input resistance, current
≤ 5 Ω
Voltage drop < 0.1 V @ I
IN
=20 mA
(current input)
Output
Number of outputs 1
Output voltage, note 0...10 V
Output current 0...20 mA, 4...20 mA
Cut-off frequency (-3 dB) > 100 Hz
load impedance voltage ≥ 10 kΩ
load impedance current ≤ 500 Ω
General data
Current-carrying capacity of cross-
connect. ≤ 20 A
Galvanic isolation
3-way isolator
Input/Output configurable
Power consumption ca. 0.6 W
Rail TS 35
Temperature coefficient
≤ 150 ppm/K of final value
Voltage supply 24 V DC ± 15 %
Insulation coordination
EMC standards DIN EN 61326
Galvanic isolation 3-way isolator
Insulation voltage 500 V
eff
/ 1 s
Insulation voltage input or output/rail 500 V
eff
/ 1 s
Insulation voltage input or output/supply500 V
eff
/ 1 s
Pollution severity
2
Rated voltage 50 V
Surge voltage category II