Brochure/Catalogue
E
E.16 2729490000
Temperature transducers
• Conversion of temperature signals, RTD
• Configuration via DIP switches
• Power supply via the output circuit
Technical data
Input
Sensor
Input measurement range
Temperature input range
Output
Output current
Sensor error detection
General data
Configuration
Voltage supply
Power consumption, max.
Storage temperature
Accuracy
Galvanic isolation
Step response time
Ambient temperature
EMC standards
Approvals
Approvals
Dimensions
Clamping range (nominal / min. / max.) mm²
Depth x width x height mm
Note
Ordering data
Note
Accessories
Note
ACT20M-RTI-CO-EOLP-S
4
3
2
1
5
6
IN
24 V
DC
230 V
AC
PLC
I, U
OUT
PT100 / 2-/3-/4-wire
PT100 -200…+850 °C
Configurable, min. measurement range 10°C (RTD)
configurable, 4...20 mA, 20…4 mA
3.5 mA ⁄ 23 mA ⁄ none
DIP switch
Output loop powered, 6…35 V
0.8 W
-40 °C...85 °C
absolute accuracy: < ±0.1 % of the measurement range, Basic
accuracy: < ±0.2°C
Without isolation
≤ 30 ms, < 300 ms
-25 °C...+70 °C
IEC 61326-1, NE 21
cULus; DETNORVER; DNVGL; EAC; FMEX; IECEXKEM; KEMAATEX
Dimensions Screw connection
2.5 / 0.5 / 2.5
114.3 / 6.1 / 112.5
Type Qty. Order No.
ACT20M-RTI-CO-EOLP-S 1 1435610000
DIN mounting rail, see accessories
Input
Output
+
4-20mA
-
+24VDC
Electrical connections
Terminal
ACT20M-RTCI-CO-OPL-S
Input Output 1
RTD
mA
2 wire 3 wire 4 wire
1 Sense- Sense-
2 R R- R-
3 R R+ R+
4 Sense+
5 ◼
6 ◻
7
8
* optional
◼ = +
◻ = –
Confi guration
Temperature range [°C]
Pt100: -200...+850 °C // TC J: -100...+1200°C // TC K: -180...+1372 °C
Min.
Temp.
S2 Max.
Temp.
S2 Max.
Temp.
S2
1 2 3 4
5 6 7 8 9
10
5 6 7 8 9
10
-200 0 170 ◼
-180 ◼ 5 ◼ 180 ◼ ◼
-150 ◼ 10 ◼ 190 ◼ ◼
-100 ◼ ◼ 15 ◼ ◼ 200 ◼ ◼ ◼
-50 ◼ 20 ◼ 225 ◼ ◼
-25 ◼ ◼ 25 ◼ ◼ 250 ◼ ◼ ◼
-10 ◼ ◼ 30 ◼ ◼ 275 ◼ ◼ ◼
-5 ◼ ◼ ◼ 35 ◼ ◼ ◼ 300 ◼ ◼ ◼ ◼
0 ◼ 40 ◼ 325 ◼ ◼
5 ◼ ◼ 45 ◼ ◼ 350 ◼ ◼ ◼
10 ◼ ◼ 50 ◼ ◼ 375 ◼ ◼ ◼
20 ◼ ◼ ◼ 55 ◼ ◼ ◼ 400 ◼ ◼ ◼ ◼
25 ◼ ◼ 60 ◼ ◼ 450 ◼ ◼ ◼
50 ◼ ◼ ◼ 65 ◼ ◼ ◼ 500 ◼ ◼ ◼ ◼
100 ◼ ◼ ◼ 70 ◼ ◼ ◼ 550 ◼ ◼ ◼ ◼
200 ◼ ◼ ◼ ◼ 75 ◼ ◼ ◼ ◼ 600 ◼ ◼ ◼ ◼ ◼
80 ◼ 650 ◼ ◼
85 ◼ ◼ 700 ◼ ◼ ◼
90 ◼ ◼ 750 ◼ ◼ ◼
95 ◼ ◼ ◼ 800 ◼ ◼ ◼ ◼
100 ◼ ◼ 850 ◼ ◼ ◼
105 ◼ ◼ ◼
110 ◼ ◼ ◼
115 ◼ ◼ ◼ ◼
120 ◼ ◼
125 ◼ ◼ ◼
130 ◼ ◼ ◼
135 ◼ ◼ ◼ ◼
140 ◼ ◼ ◼
145 ◼ ◼ ◼ ◼
150 ◼ ◼ ◼ ◼
160 ◼ ◼ ◼ ◼ ◼
◼
= On
Space-saving signal converters – ACT20M
Temperature transducers