Brochure/Catalogue

E
E.18 2729490000
Temperature transducers
Conversion of temperature signals, RTD (PT100)
Configuration via DIP switches
Technical data
Input
Sensor
Input measurement range
Temperature input range
Output
Output current
Output voltage
Load impedance current
load impedance voltage
Sensor error detection
General data
Configuration
Voltage supply
Power consumption, max.
Accuracy
Galvanic isolation
Temperature coefficient
Step response time
Ambient temperature
EMC standards
Approvals
Approvals
Dimensions
Clamping range (nominal / min. / max.) mm²
Depth x width x height mm
Note
Ordering data
Note
Accessories
Note
ACT-20M-RTI-AO-E-S
4
3
2
1
5
6
7
8
IN
24 V
DC
230 V
AC
PLC
I, U
OUT
Supply
PT100 / 2-/3-/4-wire
PT100 -200…+850 °C
Configurable, min. measurement range 10°C (RTD)
configurable, 0...20 mA, 4...20 mA
configurable, 0(2)...10 V, 0(1)...5 V
≤ 600 Ω
≥ 10 kΩ
3.5 mA ⁄ 23 mA ⁄ none
DIP switch
24 V DC ± 30 %
0.5 W
absolute accuracy: < ±0.1 % of the measurement range
Without isolation
≤0.01 % of the measurement range⁄°C or 0.02 °C ⁄ °C
≤ 30 ms
-25 °C...+70 °C
IEC 61326-1, NE 21
cULus; DETNORVER; DNVGL; EAC; FMEX; IECEXKEM; KEMAATEX
Screw connection
2.5 / 0.5 / 2.5
114.3 / 6.1 / 112.5
Type Qty. Order No.
ACT20M-RTI-AO-E-S 1 1375520000
DIN mounting rail, see accessories
Input
Output
Supply
mA
-
+
V
-
+
+
-
Terminal
ACT20M-RTI-AO-E-S
Input
Power
supply
Output 1
RTD
V mA
2 wire 3 wire 4 wire
1 Sense- Sense-
2 R R- R-
3 R R+ R+
4 Sense+
5
6
7
8
◼ = +
◻ = –
Temperature range [°C]
Pt100: -200...+850 °C
Min.
S2 Max.
Temp.
S2 Max.
Temp.
S2
1 2 3 4
5 6 7 8 9
10
5 6 7 8 9
10
-200 0 170
-180 5 180
-150 10 190
-100 15 200
-50 20 225
-25 25 250
-10 30 275
-5 35 300
0 40 325
5 45 350
10 50 375
20 55 400
25 60 450
50 65 500
100 70 550
200 75 600
80 650
85 700
90 750
95 800
100 850
105
110
115
120
125
130
135
140
145
150
160
Space-saving signal converters – ACT20M