Digital output
Valve control component for gas group IIB, 60 mA
The ACT20X-SDI-HAO-S solenoid/actuator driver takes a switched input from e.g. a safe area controller and
delivers an corresponding output to operate an actuator in a hazardous area, e.g. Zone.
This driver is suitable for switching solenoid valves or alarm devices.
EX area Zone 0, 1, 2, 20, 21, 22 Safe area Zone 2 / FM Class 1, Division 2
Channel 1:
51
52
53
54
Ex Output Signals
44
43
42
41
14
13
12
11
Input Signals
Gnd –
+19,2...31.2 V DC
Module status
Module status
42
41
44
43
N.C.
Power supply
Alarm
Solenoid
V
+
V
+
V
+
V
+
Ex label (excerpt)
ATEX FM
U
o
28 V
II 3 G Ex nA nC IIC T4 Installation in CL I DIV2 GP A-D T4
Kl. I-III ABT 1/2 GP A-G oder
Kl. I Zn2 AEx/Ex nA nC [ia] IIC T4
I
o
135 mA
II (1) G [Ex ia Ga] IIC/IIB/IIA P
o
0.95 W
II (1) D [Ex iaD] IIC
C
o
= –, L
o
= –
IECEx Example: IIB C
o
= 0.64 µF, L
o
= 7.8 mH
Ex nA nC IIC T4 Gc ATEX version, IIA C
o
= 2.1 µF, L
o
= 15.1 mH
[Ex ia Ga] IIC/IIB/IIA Ex Output Terminal (11-14)
[Ex ia Da] IIIC (More details in ATEX certicate)
Application: Inflow control in Ex zone with gas group IIB
&RQWURO
V\VWHP
$&VXSSO\
,JQLWLRQSURWHFWLRQJURXS,,&
$&7;6',+'2
9'&
&KDQQHOGLJLWDO,QSXW
9DOYHRSHQ
FORVHGVLJQDO
6ROHQRLGYDOYH
7DQN
=RQH
&KDQQHOGLJLWDO2XWSXW
(;=RQH
\
%
Output data
For gas group IIB (≤ 60 mA)
Connection terminal
Channel 1 U without load U with load I max
11-12 Min. 24 V
Min. 9 V 60 mA
Min. 11.5 V 50 mA
11-13 Min. 24 V
Min. 12.5 V 60 mA
Min. 10 V 50 mA
11-14 Min. 24 V
Min. 11 V 60 mA
Min. 13 V 50 mA
Note
Removable
terminals
(black)
LED green
= supply
Marker
Removable
terminals
(blue)
LED
SIL
SUITABLE
61508
C.18 2729490000
Intrinsically safe signal converters – ACT20X
C