Brochure/Catalogue
E
E.152729490000
Temperature transducers
• Isolation and conversion of temperature signals, (RTD
and thermocouple)
• Configuration via DIP switches
• Power supply via the output circuit
• 2-way isolation
Technical data
Input
Sensor
Input measurement range
Temperature input range
Output
Output current
Sensor error detection
General data
Configuration
Voltage supply
Power consumption, max.
Storage temperature
Accuracy
Galvanic isolation
Step response time
Ambient temperature
Insulation coordination
Insulation voltage
Rated voltage
EMC standards
Pollution degree
Overvoltage category
Approvals
Approvals
Dimensions
Clamping range (nominal / min. / max.) mm²
Depth x width x height mm
Note
Ordering data
Note
Accessories
Note
ACT20M-RTCI-CO-OLP-S
4
3
2
1
5
6
IN
I, U
OUT
24 V
DC
230 V
AC
PLC
PT100 / 2-/3-/4-wire, Thermocouple acc. to IEC 584, type: J,
Thermocouple acc. to IEC 584, type: K
PT100 -200…+850 °C, Thermocouple type J -100…+1200°C,
Thermocouple type K -200…+1370°C
Configurable, min. measurement range 10°C (RTD), min. measurement
range 50°C (TC)
configurable, 4...20 mA, 20…4 mA
3.5 mA ⁄ 23 mA ⁄ none
DIP switch
Output loop powered, 6…35 V
0.8 W
-40 °C...85 °C
absolute accuracy: < ±0.05 % of the measurement range, RTD
(PT100) Basic accuracy: < ±0.1 °C of the measurement range, TC
(J,K) Basic accuracy: < ±0.5 °C of the measurement range
2-way isolator
≤ 30 ms, < 300 ms
-25 °C...+70 °C
2.5 kV
eff
/1 min.
300 V
eff
IEC 61326-1, NE 21
2
II
cULus; DETNORVER; DNVGL; EAC; FMEX; IECEXKEM; KEMAATEX
Screw connection
2.5 / 0.5 / 2.5
114.3 / 6.1 / 112.5
Type Qty. Order No.
ACT20M-RTCI-CO-OLP-S 1 1435590000
DIN mounting rail, see accessories
Input
Output
+
-
+
4-20mA
-
+24VDC
*
RSWLRQDOH[WHUQDO
&ROG-XQFWLRQ&RPSHQVDWLRQ&-&
Electrical connections
Terminal
ACT20M-RTCI-CO-OPL-S
Input Output 1
RTD
TC mA
2 wire 3 wire 4 wire
1 Sense- Sense- CJC+*
2 R R- R- TC-/CJC-*
3 R R+ R+ TC+
4 Sense+ CJC-*
5 ◼
6 ◻
7
8
* optional
◼ = +
◻ = –
Confi guration
Temperature range [°C]
Pt100: -200...+850 °C // TC J: -100...+1200°C // TC K: -180...+1372 °C
Min.
Temp.
S2 Max.
Temp.
S2 Max.
Temp.
S2
1 2 3 4
5 6 7 8 9
10
5 6 7 8 9
10
-200 0 170 ◼
-180 ◼ 5 ◼ 180 ◼ ◼
-150 ◼ 10 ◼ 190 ◼ ◼
-100 ◼ ◼ 15 ◼ ◼ 200 ◼ ◼ ◼
-50 ◼ 20 ◼ 225 ◼ ◼
-25 ◼ ◼ 25 ◼ ◼ 250 ◼ ◼ ◼
-10 ◼ ◼ 30 ◼ ◼ 275 ◼ ◼ ◼
-5 ◼ ◼ ◼ 35 ◼ ◼ ◼ 300 ◼ ◼ ◼ ◼
0 ◼ 40 ◼ 325 ◼ ◼
5 ◼ ◼ 45 ◼ ◼ 350 ◼ ◼ ◼
10 ◼ ◼ 50 ◼ ◼ 375 ◼ ◼ ◼
20 ◼ ◼ ◼ 55 ◼ ◼ ◼ 400 ◼ ◼ ◼ ◼
25 ◼ ◼ 60 ◼ ◼ 450 ◼ ◼ ◼
50 ◼ ◼ ◼ 65 ◼ ◼ ◼ 500 ◼ ◼ ◼ ◼
100 ◼ ◼ ◼ 70 ◼ ◼ ◼ 550 ◼ ◼ ◼ ◼
200 ◼ ◼ ◼ ◼ 75 ◼ ◼ ◼ ◼ 600 ◼ ◼ ◼ ◼ ◼
80 ◼ 650 ◼ ◼
85 ◼ ◼ 700 ◼ ◼ ◼
90 ◼ ◼ 750 ◼ ◼ ◼
95 ◼ ◼ ◼ 800 ◼ ◼ ◼ ◼
100 ◼ ◼ 850 ◼ ◼ ◼
105 ◼ ◼ ◼ 900 ◼ ◼ ◼ ◼
110 ◼ ◼ ◼ 950 ◼ ◼ ◼ ◼
115 ◼ ◼ ◼ ◼ 1000 ◼ ◼ ◼ ◼ ◼
120 ◼ ◼ 1050 ◼ ◼ ◼
125 ◼ ◼ ◼ 1100 ◼ ◼ ◼ ◼
130 ◼ ◼ ◼ 1150 ◼ ◼ ◼ ◼
135 ◼ ◼ ◼ ◼ 1200 ◼ ◼ ◼ ◼ ◼
140 ◼ ◼ ◼ 1250 ◼ ◼ ◼ ◼
145 ◼ ◼ ◼ ◼ 1300 ◼ ◼ ◼ ◼ ◼
150 ◼ ◼ ◼ ◼ 1350 ◼ ◼ ◼ ◼ ◼
160 ◼ ◼ ◼ ◼ ◼ 1372 ◼ ◼ ◼ ◼ ◼ ◼
◼
= On
Space-saving signal converters – ACT20M
Temperature transducers