Brochure/Catalogue

F
F.92729490000
RTD 2-/3-conductor converter
Output-loop powered
RTD signal converter for galvanic isolation and
conversion of PT100 signals
The component draws power from the output circuit and
requires no additional auxiliary power
2-way isolation
PT100
J
U/I
V
C
Technical data
Input
Sensor
Sensor supply
Output
Output current
Load impedance, voltage/current
General data
Configuration
Ambient temperature / Storage temperature
Accuracy
Approvals
Standards
EMC standards
Dimensions
Clamping range (nominal / min. / max.) mm²
Depth x width x height mm
Note
Ordering data
0...100 °C Tension clamp connection
0...120 °C Tension clamp connection
0...150 °C Tension clamp connection
0...200 °C Tension clamp connection
0...300 °C Tension clamp connection
-50...+150 °C Tension clamp connection
-40...+100 °C Tension clamp connection
Note
Accessories
Note
MCZ PT100/3 CLP / OLP
PT100/2-/3-wire (in compliance with IEC 751)
0.8 mA / 9…30 V DC
4...20 mA (current loop) at 9...30V DC
/ ≤ 600 Ω
none
/ -25 °C...50 °C / -25 °C...85 °C
Typ.: 0.2 %, máx. 0.5 % v. FSR
CE; CSA; cURus; EAC
DIN EN 50178, DIN EN 61000-4-2
EN 61000-6
Tension-clamp connection
1.5 / 0.5 / 1.5
63.2 / 6 /
Type Qty. Order No.
MCZ PT100/3 CLP 0...100C 10 8425720000
MCZ PT100/3 CLP 0...120C 10 8483680000
MCZ PT100/3 CLP 0...150C 10 8604420000
MCZ PT100/3 CLP 0...200C 10 8473010000
MCZ PT100/3 CLP 0...300C 10 8473020000
MCZ PT100/3 CLP -50C...+150C 10 8473000000
MCZ PT100/3 CLP -40C...100C 10 8604430000
Cross-connectors for power supplies and markers: refer to accessories
Signal converters in terminal format – MCZ
Temperature transducer