Brochure/Catalogue

H
H.6 2729490000
WAVE TTA
Input and outputs can be configured on PC with the
TTA-SET software, download at www.weidmueller.
com
Universal input signals
Loop-powered or passive input
Pluggable connection terminals
Technical data
Input
Sensor
Potentiometer
Resistance
Input frequency
Input voltage
Input current
Sensor supply
Output analogue
Output voltage
Output current
Load impedance, voltage/current
Signal output
Transmit function
Output digital
Type
Switching voltage AC, max. / DC, max.
General data
Configuration
Voltage supply
Power consumption
Accuracy
Temperature coefficient
Ambient temperature / Storage temperature
Step response time
Humidity
Approvals
Insulation coordination
Standards
EMC standards
Rated voltage
Impulse withstand voltage
Pollution degree
Overvoltage category
Clearance & creepage distances
Insulation voltage
Dimensions
Clamping range (nominal / min. / max.) mm²
Depth x width x height mm
Note
WAS6 TTA / WAZ6 TTA
3-Ports IsolationAnalogue Inputs
Relay
Channel 1
Relay
Channel 2
Output
0 ... 11 V /
0 ... 22 mA
18-264 V AC/DC supply
+24 V DC
J V, I
PS
V, I
Thermocouples: B, E, J, K, L, N, R, S, T (IEC 60584), PT100, PT1000,
(EN 60571) Ni100, Ni1000, (JIS1604), Cu10, Cu25, Cu50, Cu100
(DIN 43760) 2-/3-/4-wire
10…50
Ω, 50…100 Ω, 100…200 Ω, 200…400 Ω, 400…800 Ω, 800
Ω…2 kΩ, 2…6.5 kΩ, 6.5…100 Ω
10 Ω…5 kΩ
adjustable, 2 Hz…100 kHz
-200...500 mV (min. 4 mV span), -20...50 V DC (min. 0.5 V span)
-20...+50 mA (min. interval 0.4 mA)
24 V DC / 22 mA
adjustable between -10...+10 V (min. span 2.5 V)
adjustable between 0 and 20 mA (min. span of 5 mA)
> 10 k
Ω @ 0...10 V / > 20 kΩ @ -10...+10 V / < 700 Ω
direct or inverted
Linear, x
1/2
, x
3/2
, x
5/2
or user-defined curve (101 points)
2 x 1 CO contact (hard gold-plated), Process alarms (4x) with
hysteresis, with alarm delay (configurable) 0…180 s
250 V /
Using free Windows software, TTA Set Software
18...264 V AC/DC
< 3.5 W
< 0.1 % span (DC, RTD); 0.2 % span (or 1 °C) + CJ failure
< 0.1 % / K (DC, RTD); < 0.1 % FSR / K + CJ error 0.07 °C/K
(thermocouples)
/ -40 °C...70 °C / -40 °C...85 °C
50 ms...1 sec (RTD, mV inputs), 110 ms...1 sec (V, mA inputs)
5...95 %, no condensation
CE; cULus; DNVGL; EAC
DIN EN 50178, DIN EN 61000-4-2
EN 55011, EN 61000-6
300 V
6 kV
2
III
≥ 5.5 mm (1 mm
input/output
)
2.5 kV
Screw connection Tension-clamp connection
2.5 / 0.5 / 2.5 2.5 / 0.5 / 2.5
112.4 / 45 / 112.4 / 45 /
Typical functions
I
PS
I, V
Isolator
f, I, V
PS
I, V
Converter
J
PS
I, V
Transmitter
I, V
PS
I, V
Lineariser
J
PS
Trip amplifier
Type Qty. Order No.
Screw connection
WAS6 TTA 1 8939670000
Tension-clamp connection
WAZ6 TTA 1 8939680000
CBX200 USB configuration adapter - 8978580000
Ordering data
Signal & serial interface converters –
WAVESERIES
Universal measurement transducers