Technical data
Input
Input current
Input frequency
Max. current
Voltage of measuring circuit
Sensor
Output
Output current / Output voltage
Offset current
Output signal limit
Load impedance, voltage/current
Accuracy
Temperature coefficient
Status indicator
General data
Configuration
Voltage supply
Step response time
Ambient temperature / Storage temperature
Default setting
Approvals
Insulation coordination
Standards
EMC standards
Rated voltage
Impulse withstand voltage
Pollution degree
Overvoltage category
Clearance & creepage distances
Insulation voltage
Dimensions
Clamping range (nominal / min. / max.) mm²
Depth x width x height mm
Note
Ordering data
Screw connection
Tension clamp connection
Note
Accessories
Note
1/5/10 A AC 4...20 mA
Loop-powered
I
I
IN
2
3
4...20 mA
7
9
+ 24 V
0...1 A AC/ 0...5 A AC/ 0...10 A AC
50...60Hz
100 A for 1s
250 V AC
4...20 mA (current loop) /
max. 100 µA
Approx. 24 mA
/ ≤ 600 Ω
0.5 % FSR
≤ 200 ppm/K
LED ON: OK; LED flashing: signal out of range;
LED OFF: Error
DIP switch
13...30 V DC, via output current loop
typ. 700 ms
/ 0 °C...50 °C / -20 °C...70 °C
0...5 A AC, 4...20 mA
CE; cULus; EAC
DIN EN 50178 (secure separation)
EN 55011, EN 61000-6
300 V
6 kV
2
III
≥ 5.5 mm
4 kV
eff
/ 5 s
Screw connection Tension-clamp connection
2.5 / 0.5 / 2.5 1.5 / 0.5 / 2.5
112.4 / 22.5 / 112.4 / 22.5 /
Type Qty. Order No.
WAS1 CMA LP 1/5/10A AC 1 8528650000
WAZ1 CMA LP 1/5/10A AC 1 8528660000
Cross-connectors for power supplies and markers – refer to Accessories
1/5/10 A AC 4...20 mA
Loop-powered
I
I
IN
2
3
4...20 mA
7
9
+ 24 V
0...1 A AC/ 0...5 A AC/ 0...10 A AC
50...60Hz
100 A for 1s
250 V AC
4...20 mA (current loop) /
max. 100 µA
Approx. 24 mA
/ ≤ 600
Ω
0.5 % FSR
≤ 200 ppm/K
LED ON: OK; LED flashing: signal out of range;
LED OFF: Error
DIP switch
13...30 V DC, via output current loop
typ. 700 ms
/ 0 °C...50 °C / -20 °C...70 °C
0...5 A AC, 4...20 mA
CE; cULusEX; EAC
DIN EN 50178 (secure separation)
EN 55011, EN 61000-6
300
6 kV
2
III
≥ 5.5 mm
4 kV
eff
/ 5 s
Screw connection
2.5 / 0.5 / 2.5
112.4 / 22.5 /
Type Qty. Order No.
WAS1 CMA LP 1/5/10A EX 1 8975590000
Cross-connectors for power supplies and markers – refer to Accessories
Signal & serial interface converters –
WAVESERIES
Current measuring transducers