Brochure/Catalogue

C
C.92729490000
Current output isolator
For controlling field devices located in explosion risk
zones
HART
®
Transparent
Relay output for error alarm
PC configuration with FDT/DTM software, download at
www.weidmueller.com
1 or 2 channels in one module
Technical data
Input
Input current
Voltage drop
Output analogue
Output current
Output signal limit
Load impedance current
2-wire supply
Residual ripple (current loop)
Accuracy
Temperature coefficient
Step response time
Cut-off frequency (-3 dB)
Alarm output
Type
Nominal switching voltage
Continuous current
Power rating
General data
Voltage supply
Power consumption
Ambient temperature / Storage temperature
Approvals
Approvals
Insulation coordination
Insulation voltage
Rated voltage
EMC standards
Dimensions
Clamping range (nominal / min. / max.) mm²
Depth x width x height mm
Note
Ordering data
1-channel version
Screw connection
PUSH IN connection
2-channel version
Screw connection
PUSH IN connection
Note
ACT20X-SAI-HAO-S / 2SAI-2HAO-S
OUT
DC Supply
IN
II
Ex Safe
to fieldto I/O (PLC)
4…20mA
< 2 V
4…20 mA (max. 23 mA)
< 28 mA
≤ 725 Ω
> 14.5 V @ 20 mA
< 7.5 mV
eff
< 0.1% span
< 0.01% of span/°C (TU)
≤ 5 ms
0.5…2.5 kHz @ 3.5…23 mA bi-directional HART
®
signal
Relay, 1 NO (voltage-free)
≤ 125 V AC / 110 V DC (safe area)
≤ 32 V AC / 32 V DC (zone 2)
≤ 0,5 A AC / 1 A DC (zone 2)
≤ 62.5 VA / 32 W (safe area)
≤ 16 VA / 32 W (Zone 2)
19.2…31.2 V DC
≤ 1.0 W
-20 °C...60 °C / -20 °C...85 °C
cULus; DEKRAATEX; DETNORVER; DNVGL; EAC; FMEX; FUSAFETY;
IECEXDEK
2.6 kV (input / output)
300 V
DIN EN 61326, NE 21
Screw connection PUSH IN
2.5 / 0.25 / 2.5
113.6 / 22.5 / 119.2 114.6 / 22.5 / 127.3
Type Qty. Order No.
ACT20X-SAI-HAO-S 1 8965450000
ACT20X-SAI-HAO-P 1 2456160000
ACT20X-2SAI-2HAO-S 1 8965460000
ACT20X-2SAI-2HAO-P 1 2456170000
CBX200 USB configuration adapter - 8978580000
Intrinsically safe signal converters – ACT20X
HART
®
transparent output driver