Brochure/Catalogue

D
D.112729490000
Passive isolators input loop powered
Isolation of DC– signals
Power supply via the input circuit (input loop powered)
1 or 2 channels in one module
2-way isolation
Removable terminals
Technical data
Input
Input current
Voltage drop, current input
Sensor
Number of inputs
Output
Load impedance current
Output current
Number of outputs
General data
Accuracy
Temperature coefficient
Voltage supply
Insulation coordination
EMC standards
Galvanic isolation
Impulse withstand voltage
Insulation voltage
Rated voltage
Overvoltage category
Pollution degree
Dimensions
Clamping range (nominal / min. / max.) mm²
Depth / Width / Height mm
Note
Ordering data
Channel
2-channel
1-channel
Note
Accessories
Note
ACT20P-CI-CO-ILP
OUTIN
I
I
active
11
12
41
42
0(4)...20 mA current loop
3.8 V
Current source
1
≤ 600 Ω
0…20 mA (if input: 0…20 mA), 4…20 mA (if input: 4…20 mA)
1
< 0.1 % of end value
≤ 100 ppm/K
Loop powered, via 4…20 mA input
EN 61010-1:2011, UL 61010-1, IEC61000-6-2, IEC 61000-6-4
2-way isolator
4 kV (1.2/50 µs)
2 kV inputs / outputs
300 V
III
2
Screw connection
2.5 / 0.5 / 2.5
114 / 12.5 / 117.2
Type Qty. Order No.
ACT20P-2CI-2CO-ILP-S 1 7760054124
ACT20P-CI-CO-ILP-S 1 7760054123
Passive isolators
Signal converters and monitoring
components – ACT20P