Brochure/Catalogue

D
D.16 2729490000
Temperature transducer with limit relay
Technical data
Input
Number of inputs
Potentiometer
Resistance
Sensor
Output (digital)
Alarm function
Rated switching voltage
Type
Output (analogue)
Output current
Output voltage
Load resistance current
General data
Accuracy
Configuration
Step response time
Temperature coefficient
Voltage supply
Insulation coordination
EMC standards
Impulse withstand voltage
Galvanic isolation
Insulation voltage
Rated voltage
Overvoltage category
Dimensions
Clamping range (nominal / min. / max.) mm²
Depth / Width / Height mm
Note
Ordering data
Connection type
Screw connection
PUSH IN connection
Note
Accessories
Note
ACT20P-PRO-RTCI-AO-DO
$&'&6833/<
9
*1'


3RWHQWLRPWHU5ZLUH
8,
5
1
10…150 kΩ
0…15 kΩ
PT100 / 2-/3-/4-wire, PT200, PT500, N50, N100, P 1K, N 1K, KT16,
KT81, KT82, KT83, KT84, ST13, ST20
configurable, Top and bottom limit values, window range, Short circuit
at input, Alarm delay: 0…10 s, Hysteresis 5% / 10%
24 VDC ±30%
NPN-Transitor, Switching frequency 5 kHz
configurable, 0(4)...20 mA, -20…+20 mA, ± 10mA, upscale (23 mA),
downscale (3,5 mA)
configurable, 0(1)...5 V, 0(2)...10 V, downscale (0 V), upscale (11 V),
-5…+5 V, -10...+10 V
≤ 600 Ω
< ±0.1 % of span, ≤ 2 °C (PT100)
with push-buttons and display
2- / 4- wire: 320 ms;, 3- wire / Poti: 640 ms
≤ 0.02 % / °C, ≤ 200 ppm/K
24…230 V DC ±15%, 24…230 V AC ±15% @48…62 Hz
EN 61326-1
5 kV (1.2/50 µs)
4-way isolator;, between input ⁄ output ⁄ supply
4 kV
eff
/ 1 min.
600 V
II
Screw connection PUSH IN
2.5 / 0.5 / 2.5
113.7 / 12.5 / 119.2 113.7 / 12.5 / 127.1
Type Qty. Order No.
ACT20P-PRO-RTCI-AO-DO-S 1 2448100000
ACT20P-PRO-RTCI-AO-DO-P 1 2448110000
Temperature transducers
Configurable from buttons and display
Monitoring of resistance changes
(e.g.: motor winding / heating resistors)
Analog and digital output
Removable terminals
Signal converters and monitoring
components – ACT20P