Brochure/Catalogue

E
E.8 2729490000
Signal converter
Isolation and conversion of DC signals
Configuration via DIP switches
Power supply via the mounting rail bus
3-way isolation
Support for adjustment by ACT20M Tool software,
download link at www.weidmueller.com
Technical data
Input
Input current
Input voltage
Input resistance, voltage
Voltage drop, current input
Output
Output current
Output voltage
Load impedance current
load impedance voltage
General data
Configuration
Voltage supply
Ambient temperature
Accuracy
Temperature coefficient
Cut-off frequency (-3 dB)
Power consumption, typ.
Power consumption, max.
Step response time
Insulation coordination
Insulation voltage
Rated voltage
EMC standards
Pollution degree
Overvoltage category
Approvals
Dimensions
Clamping range (nominal / min. / max.) mm²
Depth x width x height mm
Note
Ordering data
Screw connection
Note
Accessories
Note
ACT20M-AI-AO-E-S
4
3
2
1
5
6
7
8
I, U
OUT
Supply
I, U
IN
82
Supply
83
24 V
DC
230 V
AC
PLC
configurable, 0...20 mA, 4…20mA
configurable, 0(2)…10 V, 0(1)…5 V
>500 kΩ
<1,5 V
configurable, 0...20 mA, 4...20 mA
configurable, 0(2)...10 V, 0(1)...5 V
≤ 600 Ω, @ max 23mA
≥ 10 kΩ
DIP switch
24 V DC ± 30 %
0 °C...70 °C
< 0.2 % of measuring range
≤ 0.015 % / °C
100 Hz
1 W
0.8 W
≤ 7 ms
2.5 kV
eff
/1 min.
300 V
eff
IEC 61326-1, NE 21
2
II
CE; cULus; DETNORVER; DNVGL; EAC
Screw connection
2.5 / 0.5 / 2.5
114.3 / 6.1 / 112.5
Power supply optionally over the DIN mounting rail CH20M
Type Qty. Order No.
ACT20M-AI-AO-E-S 1 1176010000
DIN mounting rail, see Accessories
Input
Output
ch. 1
Supply
mA
-
+
V
-
+
+
-
Supply
+
-
-
+
Terminal
ACT20M-AI-AO-E-S
Input
Power
supply
Output 1
V mA V mA
1
2
3
4
5
6
7
8
◼ = +
◻ = –
Range
Input Output
1 2 3 4 5 6 7 8 9 10
0 … 20 mA
4 … 20 mA
0 … 10 V
2 … 10 V
0 … 5 V
1 …5 V
◼ = on
◻ = off
Space-saving signal converters – ACT20M
Signal converter