Brochure/Catalogue

E
E.10 2729490000
Passive isolator
Isolation of DC signals without additional voltage supply
Supply from the input measuring circuit
Optionally available as a 1-channel / 2-channel version
2-way isolation
Technical data
Input
Voltage drop, current input
Input current
Output
Output current
Load impedance current
General data
Configuration
Ambient temperature
Accuracy
Temperature coefficient
Cut-off frequency (-3 dB)
Power consumption
Voltage supply
Step response time
Insulation coordination
Insulation voltage
Rated voltage
EMC standards
Pollution degree
Overvoltage category
Approvals
Dimensions
Clamping range (nominal / min. / max.) mm²
Depth x width x height mm
Note
Ordering data
1-channel version
2-channel version
Note
Accessories
Note
ACT20M-CI-CO-ILP-S
4
3
2
1
5
6
7
8
I IN 1
I IN 2
I OUT 1
I OUT 2
24 V
DC
230 V
AC
PLC
PLC
1.25 V + 0.015 V
out
@25°C
0...20 mA, 4…20mA
0...20 mA, 4...20 mA
≤600 Ω
none
-25 °C...70 °C
< 0.1 % of measuring range
≤ 0.01 % / °C
100 Hz
30 mW per channel
Loop powered, via 4…20 mA input
≤ 5 ms
2.5 kV
eff
/1 min.
300 V
eff
IEC 61326-1, NE 21
2
II
cULus; DETNORVER; DNVGL; EAC; FMEX; IECEXKEM; KEMAATEX
Screw connection
2.5 / 0.5 / 2.5
114.3 / 6.1 / 112.5
Power supply optionally over the DIN mounting rail CH20M
Type Qty. Order No.
ACT20M-CI-CO-ILP-S 1 1176070000
ACT20M-2CI-2CO-ILP-S 1 1176080000
DIN mounting rail, see Accessories
Input
ch. 1
Output
ch. 1
Output
ch. 2
Input
ch. 2
+
0-20mA
-
R
Load
+
0-20mA
-
R
Load
-
+
-
+
Terminal
ACT20M-CI-2CO-S
Input 1 Output 1 Input 2 Output 2
mA mA mA mA
1
2
3
4
5
6
7
8
Terminal
ACT20M-CI-CO-ILP-S
Input 1 Output 1
mA mA
1
2
3
4
5
6
7
8
◼ = +
◻ = –
Space-saving signal converters – ACT20M
Passive isolator