Brochure/Catalogue

E
E.132729490000
Signal splitter
Isolation, conversion and doubling of DC signals
Configuration via DIP switches
Power supply via the mounting rail bus
4-way isolation
Support for adjustment by ACT20M Tool software,
download link at www.weidmueller.com
Technical data
Input
Number of inputs
Input current
Input voltage
Sensor supply
Input resistance, voltage
Voltage drop, current input
Output
Number of outputs
Output current
Output voltage
Load impedance current
load impedance voltage
General data
Configuration
Voltage supply
Ambient temperature
Accuracy
Temperature coefficient
Cut-off frequency (-3 dB)
Power consumption, typ.
Power consumption, max.
Step response time
Insulation coordination
Insulation voltage
Rated voltage
EMC standards
Pollution degree
Overvoltage category
Approvals
Dimensions
Clamping range (nominal / min. / max.) mm²
Depth x width x height mm
Note
Ordering data
Screw connection
Note
Accessories
Note
ACT20M-AI-2AO-S
4
3
2
1
5
6
7
8
I, U
OUT 1
Supply
I, U
IN
I, U
OUT 2
82
Supply
83
24 V
DC
230 V
AC
PLC
1
configurable, 0...20 mA, 4…20mA
configurable, 0(2)…10 V, 0(1)…5 V
17…28 V DC (@ 20 mA)
500 kΩ
< 1.5 V
2
Adjustable, 0...20 mA, 4...20 mA
configurable, 0(2)...10 V, 0(1)...5 V
< 300 Ω, per channel, @ max 23mA
≥ 10 kΩ
DIP switch
24 V DC ± 30 %
-25 °C...70 °C
< 0.05 % of measuring range
≤ 0.01 % / °C
100 Hz
1 W
1.2 W
≤ 7 ms
2.5 kV
eff
/1 min.
300 V
eff
IEC 61326-1, NE 21
2
II
CE; cULus; DETNORVER; DNVGL; EAC; FMEX; IECEXKEM; KEMAATEX
Screw connection
2.5 / 0.5 / 2.5
114.3 / 6.1 / 112.5
Power supply optionally over the DIN mounting rail CH20M
Type Qty. Order No.
ACT20M-AI-2AO-S 1 1176020000
DIN mounting rail, see Accessories
Input
Output
ch. 1
Supply
Output
ch. 2
mA
-
+
V
-
+
+
-
Tx
+
-
mA
-
+
V
-
+
Supply
+
-
-
+
Terminal
ACT20M-AI-2AO-S
Input
Power
supply
Output 1 Output 2
V mA mA Loop V mA V mA
1
2
3
4
5
6
7
8
◼ = +
◻ = –
Range
Input Output 1 Output 2
1 2 3 4 5 6 7 8 9 10
0 … 20 mA
4 … 20 mA
0 … 10 V
2 … 10 V
0 … 5 V
1 …5 V
0 ... 20 mA loop
4 ... 20 mA loop
◼ = on
◻ = off
Space-saving signal converters – ACT20M
Signal splitter