User Documentation

Installation
1066540000/08/12-2018 17
5. Installation
DANGER
Risk of explosion!
For installation in Zone 2, install the
module in an outer enclosure with IP
protection of at least IP54.
Protection must be according to type
of protection Ex-n or Ex-e.
WARNING
High voltage!
Before removing or mounting the unit,
turn off power supply.
NOTICE
Material damage through ESD!
Only carry out the following procedures under
ESD-safe conditions.
5.1 General
This product should only be installed by technically
qualified personnel with sufficient training in
instrumentation and control engineering.
VDE 0105 Part 1 / DIN EN 50110-1 defines qualified
personnel as electrically skilled workers,
electronically instructed personnel or personnel
meeting similar local standards.
5.1.1 Environment
This product is designed for use either indoors
(IP20) in a control panel, or in a weather-proof field
enclosure.
Avoid direct sunlight, dust, high temperatures,
mechanical vibrations and shock as well as rain
and heavy moisture.
If necessary, heating in excess of the stated limits
for ambient temperatures should be avoided by
ventilation.
Product must be installed in pollution degree 2,
overvoltage category II as defined in IEC 60664-1.
Product is designed to be safe at least under an
altitude of up to 2000 m.
5.2 Unpacking
1 Check on receipt that the product received
corresponds to the one ordered.
2 Also make sure that installation instructions have
been supplied.
3 Unpack the product carefully.
The use of stranded wires is not permitted for
mains wiring except for wires fitted with cable
ends.
Descriptions of input/output and supply
connections are shown in the block diagram and
on the side label.
The module is provided with field wiring terminals
and must be supplied from a power supply having
double/reinforced insulation.
A power switch must be easily accessible and
close to the module.
The power switch must be marked with a label
telling that it will switch off the voltage to the
module.
Year of manufacture can be taken from the first
two digits in the serial number.
Should there be any doubt as to the correct
handling of the module, contact your local
distributor.