User Documentation

Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
32 1066540000/08/12-2018
7.2.3 Electrical Connections
Terminal
Function
Connector Terminal Function Connector
mA
RTD
TC
2W 3W 4W
11 Sense Sense +
Ex input
channel 1
41 Out
output
channel 1
12 R R– R– 42 Out +
13 + R R+ R+ 43 Out
output
channel 2
14 Sense+ 44 Out +
21 Sense Sense +
Ex input
channel 2
51 GND
power
supply
22 R R– R– 52 +24 V DC
23 + R R+ R+ 53 NC
status
relay
24 Sense+ 54 COM
Table 7-4: Electrical Connections
7.2.4 Specifications
Features
Configuration and monitoring are performed via FDT/DTM Software "WI-Manager".
The device can be mounted in the safe area and in Zone 2 / Class I, Division 2 and receive signals from
Zone 0, 1, 2 and Zone 20, 21 and 22 including M1 / Class I/II/III, Division 1, Group A-G.
The passive signal inputs for RTD, TC and mA are made for one or two channels and completely
electrically isolated.
The two-channel version is suitable to use as a signal splitter.
3-way galvanic isolation between input, output and supply.
Front LEDs indicate operation status and malfunction.
The cold junction compensation for TC-signal inputs is either the internal cold junction compensation, or for
higher accuracy is an external cold junction compensation terminal available –- 1 channel 1160640000
ACT20X-CJC-HTI-S PRT 11 or 2 channel 1160650000 ACT20X-CJC-HTI-S PRT 21.
Extended self diagnostic: Monitoring of error events and cable breakage via the individual status relay.