Illustration 7-17: Applications
Current Input
Measurement range 3.5…23 mA
Alarm setpoint, low/high limit (programmable) 0…28 mA
Sensor error detection < 1 mA
Current Output
Signal range (programmable) 3.5…23 mA
Load max. 20 mA / 600 Ω / 12 V DC
Load stability 0.01 % of span /100 Ω
Sensor error detection (programmable) 3.5 mA / 23 mA / none
Current limit 28 mA
Effect of supply voltage change < ±10 μA