Approval/Certificate/Document of Conformity

Annex 1 to: Certificate of Conformity IECEx DEK 11.0050X
Report NL/DEK/ExTR11.0079/02
Page 1 of 1
Form 124
Version 3 (2018-03)
DEKRA Certification B.V. Meander 1051, 6825 MJ Arnhem P.O. Box 5185, 6802 ED Arnhem The Netherlands
T +31 88 9683000 F +31 88 9683100 www.dekra-certification.com Registered Arnhem 09085396
Electrical data
Supply (terminals 51, 52): U = 19.2 ... 31.2 Vdc.
Status-Relay output (terminals 53, 54):
U ≤ 32 Vac or 32 Vdc, I ≤ 0.5 Aac or I ≤ 1 Adc respectively.
If the repeater is installed outside the hazardous area, the following data for the relay contacts apply: U ≤
110 Vdc or 125 Vac, I ≤ 0.3 Adc or I ≤ 0.5 Aac respectively.
Outputs (terminals 41, 42 resp. 43, 44): I = 4 - 20 mA.
For all circuits above: U
m
= 253 Vac (max. frequency 400 Hz).
Loop current input (terminals 13, 14 resp. terminals 23, 24):
in type of protection intrinsic safety Ex ia IIC/IIB/IIA/IIIC/I, with following maximum values:
U
o
= 28 V; I
o
= 93 mA; P
o
= 0.65 W;
C
o
= 0.08 µF (IIC) or 0.6 µF (IIB) or 2.15 µF (IIA) or 3.76 µF (I);
L
o
= 3 mH (IIC) or 12 mH (IIB) or 25 mH (IIA) or 30 mH (I);
For group IIIC, the parameters of group IIB apply.
Current input (terminals 11, 12 resp. terminals 21, 22):
in type of protection intrinsic safety Ex ia IIC/IIB/IIA/IIIC/I, for connection to a certified intrinsically safe circuit,
with following maximum values:
U
i
= 30 V; Ii = 120 mA; Pi = 0.85 W; C
i
= 2 nF; L
i
= 0 µH;
U
o
= 0 V; I
o
= 0 mA; P
o
= 0 mW.
Both circuits of one channel are not used simultaneously.
The input circuits of both channels are infallibly galvanically isolated from each other and from the non-
intrinsically safe supply and output circuits.
Combination of current loop input of channel 1 and current input of channel 2, where terminal 13 is
connected to terminal 21:
Current loop circuit (terminals 14 and 22) is in type of protection intrinsic safety Ex ia IIC/IIB/IIA/IIIC/I, with
following maximum values:
U
o
= 28 V; I
o
= 93 mA; P
o
= 0.65 W;
C
o
= 0.08 µF (IIC) or 0.6 µF (IIB) or 2.15 µF (IIA) or 3.76 µF (I);
L
o
= 3 mH (IIC) or 12 mH (IIB) or 25 mH (IIA) or 30 mH (I).
For group IIIC, the parameters of group IIB apply.
Combination of current inputs of both channels in series, where terminal 11 is connected to terminal 22:
Current input (terminals 12 and 21) is in type of protection intrinsic safety Ex ia IIC/IIB/IIA/IIIC/I, for
connection to a certified intrinsically safe circuit, with following maximum values:
U
i
= 30 V; Ii = 120 mA; Pi = 0.85 W; C
i
= 4 nF; L
i
= 0 µH;
U
o
= 0 V; I
o
= 0 mA; P
o
= 0 mW. `