ACT20X Manual
Revision History Version Date Change 0.0 02/2009 First Edition 1.0 12/2011 Further products complemented 2.0 02/2014 Updating of ATEX and IEC labeling Further products complemented 3.0 05/2014 Updating of application illustrations 4.0 09/2014 Application illustrations 7-6, 7-12, 7-17 corrected 5.0 11/2014 Updating of product pictures 6.0 03/2015 Application illustration 7-3 corrected 7.0 06/2016 Mounting illustrations Appendix G corrected 8.
Contents Contents Revision History ............................................................................................................................................... 3 Contact Address ............................................................................................................................................... 3 Contents ............................................................................................................................. 4 1. Approvals................
Contents 5.1 General ............................................................................................................................................. 17 5.1.1 Environment ............................................................................................................................ 17 5.2 Unpacking ........................................................................................................................................ 17 5.3 Mounting ..........................
Contents 7.5 7.6 7.7 7.8 7.4.3 Electrical Connections ............................................................................................................ 48 7.4.4 Specifications .......................................................................................................................... 48 ACT20X-HAI-SAO (HART-transparent Repeater) ......................................................................... 56 7.5.1 Description ...................................................
Contents ATEX Installation Drawing....................................................................................................................157 IECEx Installation Drawing ...................................................................................................................167 FM Installation Drawing ........................................................................................................................177 Appendix F.
Approvals 1. Approvals 1.1 CE These products fulfill the guidelines issued by the European Union and are therefore entitled to carry the CE mark. DEKRA Certification B.V. II (1) D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I 1.6 IECEx In accordance with: - IEC 60079-0:2011 1.2 EMC In accordance with: - EN 61326-1:2006 - IEC 60079-11:2011 - IEC 60079-15:2010 - IEC 60079-26:2007 IECEx marking: 1.3 LVD In accordance with: - EN 61010-1:2010 1.
Approvals 1.8 SIL 1.9 EAC 1066540000/08/12-2018 1.
Warranty Statement 2. Warranty Statement 2.1 36 Months Warranty Weidmüller gives a 36 months warranty on the product in accordance with the warranty terms as described in the general business conditions of the Weidmüller company which has sold the products to you. Weidmüller guarantees that defects which have already existed at the time when the risk passed will be repaired by Weidmüller free of charge or Weidmüller will provide a new, functionally equivalent product to replace the defective one.
Safety Instructions 3. Safety Instructions 3.1 Approved Use This product is intended for use in applications as described in the operating instructions only. Any other utilization is not permitted and can lead to accidents or destruction of the device. Using the device in non-approved applications will immediately void all guarantee and warranty claims on the part of the operator against the manufacturer. 3.
Safety Instructions 3.6 Symbol Identification 3.7 Electrical Precautions DANGER WARNING Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. High voltage! • Before removing or mounting the unit, turn off power supply. Follow ESD installation regulations, including EMI precautions. WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. 3.
Introduction 4. Introduction 4.1 Product Description 4.1.1 Product Family ACT20X Order No.
Introduction 8965490000 2456200000 Table 4-1: 14 ACT20X-HUI-SAO-S ACT20X-HUI-SAO-P Universal converter universal analog in (from Ex) to analog (V / mA) + trip relay out Family ACT20X 1066540000/08/12-2018
Introduction 4.1.2 General Description Weidmüller’s ACT20X – new signal converters for hazardous areas: Universal family of products covers the entire field of hazardous area applications with six different basic functions. With the introduction of its ACT20X modules Weidmüller is offering a completely new family of signal converters for hazardous area applications. With just 11 mm per channel these compactly designed modules require very little space in the electrical cabinet.
Introduction 4.1.3 The Six Basic Module Types in Detail NAMUR Pulse Isolator The pulse isolator ACT20X-HDI-SDO is a special signal isolator/converter for NAMUR sensor signals from within Ex Zone 0. Transistor or relay outputs are available on the output side.
Installation 5. Installation DANGER 5.2 Risk of explosion! 1 Check on receipt that the product received corresponds to the one ordered. • For installation in Zone 2, install the module in an outer enclosure with IP protection of at least IP54. • Protection must be according to type of protection Ex-n or Ex-e. WARNING High voltage! • Before removing or mounting the unit, turn off power supply. NOTICE Material damage through ESD! • Only carry out the following procedures under ESD-safe conditions. 5.
Installation, Mounting 5.3 Mounting The product is designed to be mounted onto a TS 35 DIN rail. 5.4 Marking A device marker is located below the upper set of terminals for costumer identification. It clips onto the rail via a spring-loaded mounting foot and can be removed via a spring release on the edge of the product near the mounting rail.
Installation 5.5 Electrical Connections See section 7, "Product Installation / Operation” for further information. 5.5.1 EMI Protection 5.6 Calibration and Adjustment • During calibration and adjustment, carry out the measuring and connection of external voltages according to the specifications in this manual. • Only use tools and instruments that are safe to use. NOTICE Do not install input, output and power supply cables close to sources of electrical interference! 5.
Installation, Encoding 5.8 Encoding NOTICE Leaving the product connectors uncoded results in lack of interchanging protection. All connectors will be identically encoded. 2 Plug encoded connector onto pin header. Encoding element is transferred from connector to pin header. Encoding element remains in the pin header housing. • Create connector coding plan prior to first mating and encode connectors accordingly. • Perform encoding procedure for each new module.
Installation 5.9 Configuration DANGER 2 Connect the CBX200 USB jack, as shown in the illustration: Configuration must be performed in a safe area! Configuration is performed via a connector located behind the front flap. 1 Open the front flap, as shown in the illustration: Illustration 5-9: 1 2 3 CBX200 USB Connection Jack connection under front flap CBX200 with USB connection PC 3 See "WI-Manager" documentation for further information.
Operation, Normal Operation 6. Operation 6.1 Normal Operation Operators are only allowed to adjust and operate modules that are safely fixed in panels, etc., thus avoiding the danger of personal injury and damage. This means there is no electrical shock hazard and the module is easily accessible. 6.2 6.3 Cleaning 1 Power supply switched off. 2 Clean with cloth moistened with distilled water. Warm-Up The product is designed to start-up as soon as power is supplied.
Product Installation / Operation 7. Product Installation / Operation 7.1 ACT20X-HDI-SDO (NAMUR Pulse Isolator) 7.1.1 Description The pulse isolator ACT20X-HDI-SDO is a special signal isolator/converter for NAMUR sensor signals from within Ex Zone 0. The product is able for an intrinsically safe operation of NAMUR sensors or for contacts with floating and resistance circuits. Transistor or relay outputs are available on the output side. A dual-channel version is optionally available.
Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator) 7.1.
Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator) 7.1.3 Electrical Connections Terminal Function 11 SW Sense 12 NAMUR − 13 SW Supply 14 Connector Terminal Function 41 COM / 42 NO / NC / OPTO – 43 COM / NAMUR + 44 NO / NC / OPTO – 21 SW Sense 51 GND 22 NAMUR − 52 +24 V DC 23 SW Supply 53 NC 24 NAMUR + 54 COM Table 7-2: 7.1.
Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator) Illustration 7-2: 26 Functional Block Diagram 1066540000/08/12-2018
Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator) Illustration 7-3: Applications Input NAMUR / Mechanical Switch with Series and Parallel Resistance NAMUR sensor, according to EN 60947-5-6 Mechanical Switch, Series resistance (RS) nom. 750 Ω Mechanical Switch, Parallel resistance (RP) nom. 15 kΩ Frequency range 0…5 kHz Min. pulse length > 0.1 ms Resistance nom. 1 kΩ Trigger level, signal < 1.2 mA, > 2.1 mA Trigger level, cable fault < 0.1 mA, > 6.
Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator) Status Relay Safe Area Zone 2 Installation Voltage max. 125 V AC / 110 V 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A 0.5 A AC / 1 A DC Power max. 62.5 VA / 32 W 16 VA / 32 W Relay Output Safe Area Zone 2 Installation Voltage max. 250 V AC / 30 V 32 V AC / 30 V DC Current max. 2 A AC / 2 A DC 2 A AC / 2 A DC Power max. 500 VA / 60 W 16 VA / 60 W Max. switching frequency 20 Hz Opto NPN Output Max.
Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator) General Specifications Communications interface, adapter / configuration software / FDT-DTM device driver CBX200 USB / "WI-Manager" / ACT20X DTM Dimensions (H x W x D) 105.6 x 22.5 x 114.7 mm Protection degree IP20 Screw terminal torque 0.5 Nm Vibration IEC 60068-2-6, test Fc, 1g, 2…100 Hz Vibration, continuous IEC 60068-2-64, test Fh, 1g, 3…100 Hz Wire size, stranded wire AWG 26…14 / 0.13…2.
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter) 7.2 ACT20X-HTI-SAO (Temperature/mA Converter) 7.2.1 Description The modules of the ACT20X-HTI-SAO family transmit analog signals galvanic isolated from hazardous areas to the safe area. The input circuits are designed intrinsically safe. The ACT20X-HTI-SAO converts and isolates current and temperature sensor signals (mA, RTD and TC). The two-channel version ACT20X-2HTI-2SAO can be used as a signal splitter for mA signals.
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter) 7.2.
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter) 7.2.3 Electrical Connections Function Terminal mA RTD 2W 11 Connector output channel 1 Sense– + 41 Out − – 42 Out + 43 Out − 44 Out + 51 GND 52 +24 V DC 53 NC 54 COM R– R– 13 + R R+ R+ 14 Ex input channel 1 Sense+ Sense– Sense– + – 22 – R R– R– 23 + R R+ R+ Ex input channel 2 Sense+ Table 7-4: Connector Sense– R 24 Function 4W – 21 Terminal 3W 12 7.2.
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter) Illustration 7-5: Functional Block Diagram 1066540000/08/12-2018 33
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter) Illustration 7-6: Applications RTD Input Pt100, according to -200…+850 °C, IEC 60751 Ni100, according to -60…+250 °C, DIN 43760 Sensor types (* = without short circuit detection) Pt10*, Pt20*, Pt50*, Pt100, Pt250, Pt300, Pt400, Pt500, Pt1000, Ni50, Ni100, Ni120, Ni1000 Cable resistance per wire (max.) 50 Ω Sensor current nom. 0.2 mA Effect of sensor cable resistance (3/4-wire) < 0.
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter) TC Input, Sensor Types Temperature Range Standard B 0…+1820 °C IEC 60584-1 E -100…+1000 °C IEC 60584-1 J -100…+1200 °C IEC 60584-1 K -180…+1372 °C IEC 60584-1 L -200…+900 °C DIN 43710 N -180…+1300 °C IEC 60584-1 R -50…+1760 °C IEC 60584-1 S -50…+1760 °C IEC 60584-1 T -200…+400 °C IEC 60584-1 U -200…+600 °C DIN 43710 W3 0…+2300 °C ASTM E988-90 W5 0…+2300 °C ASTM E988-90 LR -200…+800 °C GOST 3
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter) TC Input, Cold Junction Compensation (CJC) CJC: external with ACT20X-CJC-HTI (1160640000 or 1160650000) +20…+28 °C ≤ ±1 °C -20…+20 °C and +28…+60 °C≤ ±1.6 °C CJC via internal sensor ∆t = internal temperature – ambient temperature ±(2.0 °C + 0.2 °C * ∆t) Sensor error detection (programmable, only wire breakage) ON/OFF Sensor error current: when detecting else nom.
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter) Status Relay Safe Area Zone 2 Installation Voltage max. 125 V AC / 110 V 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A 0.5 A AC / 1 A DC Power max. 62.5 VA / 32 W 16 VA / 32 W Power Supply Supply voltage 19.2…31.2 V DC Max. consumption (2-channels) ≤ 3.5 W Fuse 1.25 A / 250 V AC Isolation Voltages (reinforced insulation), Test/Operation Inputs / outputs / supply 2.6 kV AC / 300 V AC Output 1 to output 2 1.
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter) Average response time incl. delay: Temperature input mA input ≤1s ≤ 0.
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver) 7.3 ACT20X-SDI-HDO (Solenoid/Alarm Driver) 7.3.1 Description The ACT20X-SDI-HDO is a solenoid/alarm driver for the control of solenoids, acoustic alarms and LEDs mounted in the hazardous area (Ex Zone 0). Optionally one or two channel versions available. The following solenoid/alarm drivers are available: Order No.
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver) 7.3.
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver) 7.3.3 Electrical Connections Terminal Function 11 GND 12 Ex 1 13 Ex 2 14 Terminal Function Connector 41 In − 42 In + input channel 1 43 In − Ex 3 44 In + 21 GND 51 GND 22 Ex 1 52 +24 V DC 23 Ex 2 53 COM 24 Ex 3 54 NC Table 7-6: 7.3.
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver) Illustration 7-8: 42 Functional Block Diagram 1066540000/08/12-2018
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver) Illustration 7-9: Applications NPN Input (NPN and mechanical switch) Trigger level (low) ≤ 2 V DC Trigger level (high) ≥ 4 V DC Max. external voltage 28 V DC Input impedance 3.5 kΩ PNP Input Trigger level (low) ≤ 8 V DC Trigger level (high) ≥ 10 V DC Max. external voltage 28 V DC Input impedance 3.
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver) Output Output ripple ACT20X-SDI-HDO-L, ACT20X-2SDI-HDO, low current (< 35 mA), Ex barrier data channel 1 < 40 mV RMS Vout no load Vout with load Iout max. 11–12 min. 24 V min. 12.5 V 35 mA 11–13 min. 24 V min. 13.5 V 35 mA 11–14 min. 24 V min. 14.5 V 35 mA Vout no load Vout with load Iout max. 21–22 min. 24 V min. 12.5 V 35 mA 21–23 min. 24 V min. 13.5 V 35 mA 21–24 min. 24 V min. 14.
Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver) Power Supply Supply voltage 19.2…31.2 V DC Max. consumption (2-channels) ≤ 3.5 W Fuse 1.25 A / 250 V AC EMC immunity influence < ±0.5 % of span Extended EMC immunity: NAMUR NE 21, A criterion, burst < ±1 % of span Isolation Voltages (reinforced insulation), Test/Operation Inputs / outputs / supply 2.6 kV AC / 300 V AC Output 1 to output 2 1.5 kV AC / 150 V AC Status relay to supply 1.
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter) 7.4 ACT20X-HUI-SAO (Universal Converter) 7.4.1 Description The device ACT20X-HUI-SAO transmits analog signals from hazardous areas safely galvanically separated into non or less hazardous areas. The input circuits are designed intrinsically safe. The ACT20X-HUI-SAO converts and isolates current, voltage, potentiometer and temperature sensor signals (mA, V, potentiometer, RTD and TC).
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter) 7.4.
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter) 7.4.3 Electrical Connections Function Terminal Terminal Function 41 Out − M3 42 Out + 2W /3W / 4W M1 43 COM 4W M2 44 NO 51 +24 V DC 52 GND 53 NC 54 COM TC RTD 11 + 3W / 4W 12 – / CJC 2W / 3W / 4W 13 CJC 14 21 POT V mA – 22 – + 24 + Table 7-8: 7.4.
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter) Illustration 7-11: Functional Block Diagram 1066540000/08/12-2018 49
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter) Illustration 7-12: Applications RTD, Resistance and Potentiometer Input Pt100, according to -200…+850 °C, IEC 60751 Ni100, according to -60…+250 °C, DIN 43760 Resistance (without short circuit detection in the range R = 0…18Ω, appr.
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter) TC Input, Sensor Types Temperature Range Standard B 0…+1820 °C IEC 60584-1 E -100…+1000 °C IEC 60584-1 J -100…+1200 °C IEC 60584-1 K -180…+1372 °C IEC 60584-1 L -200…+900 °C DIN 43710 N -180…+1300 °C IEC 60584-1 R -50…+1760 °C IEC 60584-1 S -50…+1760 °C IEC 60584-1 T -200…+400 °C IEC 60584-1 U -200…+600 °C DIN 43710 W3 0…+2300 °C ASTM E988-90 W5 0…+2300 °C ASTM E988-90 LR -200…+800 °C GOST 3044-8
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter) TC Input, Cold Junction Compensation (CJC) CJC: external with ACT20X-CJC-HTI (1160640000) +20…+28 °C ≤ ±1 °C -20…+20 °C and +28…+60 °C ≤ ±1.6 °C CJC via internal sensor ∆t = internal temperature – ambient temperature ±(2.0 °C + 0.4 °C * ∆t) Sensor error detection (programmable, only wire breakage) ON/OFF Sensor error current: when detecting else nom.
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter) 2-wire 4…20 mA Output Signal range 4…20 mA Load resistance ≤ (Vsupply – 3.5 V) / 0.023 A [Ω] Load stability ≤ 0.01 % of span / 100 Ω Max. external 2-wire supply 3.5…26 V DC Effect of external 2-wire supply voltage variation < 0.005 % of span / V Relay Output Safe Area Zone 2 Installation Voltage max. 250 V AC / 30 V DC 32 V AC / 30 V DC Current max. 2 A AC / 2 A DC 2 A AC / 2 A DC Power max.
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter) Environmental Specifications Ambient temperature -20…+60 °C Storage temperature -20…+85 °C Relative humidity (non-condensation) < 95 % Calibration temperature +20…28 °C General Specifications Communications interface, adapter / configuration software / FDT-DTM device driver CBX200 USB / "WI-Manager" / ACT20X DTM Dimensions (H x W x D) 105.6 x 22.5 x 114.7 mm Protection degree IP20 Screw terminal torque 0.
Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter) Contact function Normally Open (NO) Setpoint 50 °C (input type temperature) / 50 % Activation direction Increasing Hysteresis 1 °C (input type temperature) / 1 % Action on error Relay OPEN Activation delay 0s Deactivation delay 0s Illustration 7-13: Graphic depiction of window Illustration 7-14: Graphic depiction of setpoint 1066540000/08/12-2018 55
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater) 7.5 ACT20X-HAI-SAO (HART-transparent Repeater) 7.5.1 Description The ACT20X-HAI-SAO current supply isolator is a HART-protocol, transparent isolator for analogue input signals from Ex Zone 0. The input may also operate as an active current loop (the loop current provided by the device). It provides an 4...20 mA current signal for the safe zone on the output side. It is available in a single-channel or two-channel version.
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater) 7.5.
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater) 7.5.3 Electrical Connections Terminal Function 11 I Passive − 12 I Passive + 13 I Active Return 14 Terminal Function Connector 41 Out − 42 Out + output channel 1 43 Out − I Active Supply 44 Out + 21 I Passive − 51 GND 22 I Passive + 52 +24 V DC 23 I Active Return 53 NC 24 I Active Supply 54 COM Table 7-10: 7.5.
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater) Illustration 7-16: Functional Block Diagram 1066540000/08/12-2018 59
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater) Illustration 7-17: Applications Current Input Measurement range 3.5…23 mA Alarm setpoint, low/high limit (programmable) 0…28 mA Sensor error detection < 1 mA Current Output Signal range (programmable) 3.5…23 mA Load max. 20 mA / 600 Ω / 12 V DC Load stability ≤ 0.01 % of span /100 Ω Sensor error detection (programmable) 3.
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater) 2-wire 4…20 mA Current Loop Output Signal range 3.5...23 mA Load resistance ≤ (Vsupply – 3.5 V) / 0.023 A [Ω] Load stability ≤ 0.01 % of span/100 Ω External 2-wire supply voltage 3.5…26 V DC Effect of external 2-wire supply voltage change < 0.005 % of span / V Accuracy Absolute Accuracy Temperature Coefficient General values ≤ ±0.1 % of span ≤ ±0.01 % of span / °C Basic values ≤ ±16 µA ≤ ±1.
Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater) General Specifications Communications interface, adapter / configuration software / FDT-DTM device driver CBX200 USB / "WI-Manager" / ACT20X DTM Dimensions (H x W x D) 105.6 x 22.5 x 114.7 mm Protection degree IP20 Screw terminal torque 0.5 Nm Vibration IEC 60068-2-6, test Fc, 1g, 2…100 Hz Vibration, continuous IEC 60068-2-64, test Fh, 1g, 3…100 Hz Wire size, stranded wire AWG 26…14 / 0.13…2.
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver) 7.6 ACT20X-SAI-HAO (HART-transparent Driver) 7.6.1 Description The ACT20X-SAI-HAO is a HART-protocol, transparent current output isolator. A DC current input signal from the safe area will be galvanically separated and drives controlled field devices in Ex Zone 0. It is available in a single-channel or two-channel version. The following HART-transparent drivers are available: Order No.
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver) 7.6.
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver) 7.6.3 Electrical Connections Terminal Function 11 Out − 12 Out + 13 Connector Terminal Function Connector 41 In – 42 In + input channel 1 43 In – 44 In + 51 GND 52 +24 V DC 53 NC 54 COM Ex output channel 1 14 21 Out − 22 Out + 23 Ex output channel 2 24 Table 7-12: 7.6.4 input channel 2 power supply status relay Electrical Connections Specifications Features • HART-compatible for 0.5...2.
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver) Illustration 7-19: 66 Functional Block Diagram 1066540000/08/12-2018
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver) Illustration 7-20: Applications Current Input Measurement range 3.5…23 mA Input resistance nom. 20 Ω + PTC 50 Ω Alarm setpoint, low/high limit (programmable) 0…28 mA Sensor error detection < 1 mA Current Output Signal range (programmable) 3.5…23 mA Load max. 20 mA / 725 Ω / 14.5 V DC Load stability ≤ 0.01 % of span / 100 Ω Sensor error detection (programmable) 3.
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver) Accuracy Absolute Accuracy Temperature Coefficient General values ≤ ±0.1 % of span ≤ ±0.01 % of span / °C Basic values ≤ ±16 µA ≤ ±1.6 µA / °C Status Relay Safe Area Zone 2 Installation Voltage max. 125 V AC / 110 V 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A 0.5 A AC / 1 A DC Power max. 62.5 V AC / 32 W 16 VA / 32 W Power Supply Supply voltage 19.2…31.2 V DC Max. consumption (2-channels) ≤ 3.
Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver) EMC immunity influence ≤ ±0.5 % of span Extended EMC immunity: NAMUR NE 21, A criterion, burst ≤ ±1 % of span HART Communication Frequency range 0.5…2.5 kHz Signal / noise ratio min. 60 dB (0.5…10 kHz) Response time (0…90 %, 100…10 %) < 5 ms Default Settings Low/high limit 1066540000/08/12-2018 3.8 mA / 20.
Product Installation / Operation, ACT20-FEED-IN-PRO 7.7 ACT20-FEED-IN-PRO 7.7.1 Description The power feed-in unit ACT20-FEED-IN-PRO supplies the devices on the CH20M DIN rail bus with 24 V DC. At the same time, the ACT20-FEED-IN-PRO device reads the group error contact – optionally provided by the installed devices – from the CH20M rail bus and sends a message through the status relay to the external controller.
Product Installation / Operation, ACT20-FEED-IN-PRO 7.7.
Product Installation / Operation, ACT20-FEED-IN-PRO 7.7.3 Electrical connections Terminal Function 41 NO 42 COM 43 NC Connector status relay 44 51 GND 52 +24 V DC 53 +24 V DC 54 GND 81 collective error contact 82 +24 V DC 83 GND power supply backup power supply Weidmüller DIN rail bus CH20M 84 85 Table 7-14: 7.7.
Product Installation / Operation, ACT20-FEED-IN-PRO Illustration 7-22: Functional Block Diagram 1066540000/08/12-2018 73
Product Installation / Operation, ACT20-FEED-IN-PRO * If the backup power supply is not required, the included jumper must be employed between terminal 52 and 53. Illustration 7-23: Applications Input Supply Voltage Supply voltage 21.6…26.4 V DC Backup supply voltage 21.6…26.4 V DC Trigger level for collective alarm on DIN rail bus < 21 V DC Efficiency > 97.9 % Internal consumption max.
Product Installation / Operation, ACT20-FEED-IN-PRO Output Power Supply Output voltage at 4 A Vinput power supply – 0.5 V DC Output current max. 4 A DC Output power max. 96 W Status Relay (Alarm),Safe Area Voltage max. 250 V AC / 30 V DC Current max. 2 A AC / 2 A DC Power max. 500 VA / 60 W Environmental Specifications Ambient temperature -20…+60 °C Storage temperature -20…+85 °C Relative humidity (non-condensation) < 95 % General Specifications Dimensions L x W x H 109.2 x 22.5 x 113.
Product Installation / Operation, Female Plug BHZ 5.00 7.8 Female Plug BHZ 5.00 7.8.1 Description Among other things, the following female plug is available: Order No. Type Description 1069380000 BHZ 5.00/04/90LH BK/BL Female plug Features • Simple, component-friendly unplugging of the female plug using the integrated release lever.
Product Installation / Operation, Female Plug BHZ 5.00 7.8.2 Specifications General Specifications Product family OMNIMATE Housing - series CH20M Wire connection method Clamping yoke connection Conductor outlet direction 90° Pitch 5 mm / 0.197 inch Number of poles 4 Screwdriver blade DIN 5264 0.6 x 3.5 Tightening torque 0.4...0.6 Nm Clamping screw M 2.5 Stripping length 8 mm Dimensions L x W x H 14.6 x 22.4 x 29 mm Connectable Wires Clamping range 0.13...3.
Product Installation / Operation, Female Plug BHZ 5.
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator) Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator) ATEX Installation Drawing The module is available in the following variants: Order No.
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator) CBX200 – "WI-Manager" Software For installation in Zone 2 / Division 2 the following must be observed: - The CBX200 is an interface cable for configuration via PC. - Configuration must be performed only in a safe area.
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator) Illustration 7-24: ATEX Installation Drawing, (450102 Sheet 1-2, 450588 Sheet 1-2, 450589 Sheet 1-2, 450590 Sheet 1-2) Terminal CH1 (11, 12, 13, 14), CH2 (21, 22, 23, 24) Ex Input Uo 10.6 V DC Io 12 mA DC Po 32 mW Lo/Ro 1150 µH/Ω Group Co Lo IIC 2 µF 260 mH IIB 6 µF 780 mH IIA 18 µF 1000 mH I 90 µF 1000 mH Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 1066540000/08/12-2018 253 V, max.
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator) Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Power max. 3W Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.5 VA / 32 W 16 VA / 32 W Terminal CH1 (41, 42) and CH2 (43, 44) Digital Output, NPN Output Voltage max. 30 V DC Current max.
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator) IECEx Installation Drawing The module is available in the following variants: Order No.
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator) CBX200 – "WI-Manager" Software For installation in Zone 2 / Division 2 the following must be observed: - The CBX200 is an interface cable for configuration via PC. - Configuration must be performed only in a safe area. IECEx Certificate KEM 09.
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator) Illustration 7-25: IECEx Installation Drawing, (450102 Sheet 3-4, 450588 Sheet 3-4, 450589 Sheet 3-4, 450590 Sheet 3-4) Terminal CH1 (11, 12, 13, 14), CH2 (21, 22, 23, 24) Ex Input Uo 10.6 V DC Io 12 mA DC Po 32 mW Lo/Ro 1150 µH/Ω Group Co Lo IIC 2 µF 260 mH IIB 6 µF 780 mH IIA 18 µF 1000 mH I 90 µF 1000 mH Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 1066540000/08/12-2018 253 V, max.
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator) Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Power max. 3W Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.5 VA / 32 W 16 VA / 32 W Terminal CH1 (41, 42) and CH2 (43, 44) Digital Output, NPN Output Voltage max. 30 V DC Current max.
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator) FM Installation Drawing The module is available in the following variants: Order No.
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator) Use 60/75 °C copper conductors in the wire size AWG 26-14. The year of manufacture can be taken from the first two digits in the serial number. CBX200 – "WI-Manager" Software For installation in Zone 2 / Division 2 the following must be observed: - The CBX200 is an interface cable for configuration via PC. - Configuration must be performed only in a safe area.
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator) Illustration 7-26: FM Installation Drawing, (450102 Sheet 5-6, 450588 Sheet 5-6, 450589 Sheet 5-6, 450590 Sheet 5-6) Terminal CH1 (11, 12, 13, 14), CH2 (21, 22, 23, 24) Ex Input Uo, Vt 10.
Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator) Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Power max. 3W Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter) Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter) ATEX Installation Drawing The module is available in the following variants: Order No.
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter) CBX200 – "WI-Manager" Software For installation in Zone 2 / Division 2 the following must be observed: - The CBX200 is an interface cable for configuration via PC. - Configuration must be performed only in a safe area.
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter) Illustration 7-27: ATEX Installation Drawing (1), (450594 Sheet 1-2, 450595 Sheet 1-2) Terminal CH1 (11, 12, 13, 14), CH2 (21, 22, 23, 24) Ex Input Uo 8.7 V Io 18.
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter) Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter) Illustration 7-28: ATEX Installation Drawing (2), (450594 Sheet 1-2, 450595 Sheet 1-2) Terminal CH1 (13), CH2 (22) Ex Input Uo 17.4 V Io 18.4 mA Po 80 mW Lo/Ro 445 µH/Ω Ui 10 V Ii 30 mA Ci 15 nF Li 1.7 µH Group Co Lo IIC 0.3 µF 80 mH IIB 1.
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter) Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter) IECEx Installation Drawing The module is available in the following variants: Order No.
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter) CBX200 – "WI-Manager" Software For installation in Zone 2 / Division 2 the following must be observed: - The CBX200 is an interface cable for configuration via PC. - Configuration must be performed only in a safe area. IECEx Certificate KEM 09.
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter) Illustration 7-29: IECEx Installation Drawing (1), (450594 Sheet 3-4, 450595 Sheet 4-6) Terminal CH1 (11, 12, 13, 14), CH2 (21, 22, 23, 24) Ex Input Uo 8.7 V Io 18.
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter) Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter) Illustration 7-30: IECEx Installation Drawing (2), (450594 Sheet 3-4, 450595 Sheet 4-6) Terminal CH1 (13), CH2 (22) Ex Input Uo 17.4 V Io 18.4 mA Po 80 mW Lo/Ro 445 µH/Ω Ui 10 V Ii 30 mA Ci 15 nF Li 1.7 µH Group Co Lo IIC 0.3 µF 80 mH IIB 1.
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter) Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter) FM Installation Drawing The module is available in the following variants: Order No.
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter) CBX200 – "WI-Manager" Software For installation in Zone 2 / Division 2 the following must be observed: - The CBX200 is an interface cable for configuration via PC. - Configuration must be performed only in a safe area.
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter) Illustration 7-31: FM Installation Drawing (1), (450594 Sheet 5-6, 450595 Sheet 7-9) Terminal CH1 (11, 12, 13, 14), CH2 (21, 22, 23, 24) Ex Input Uo, Vt 8.7 V Io, It 18.
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter) Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter) Illustration 7-32: FM Installation Drawing (2), (450594 Sheet 5-6, 450595 Sheet 7-9) Terminal CH1 (13), CH2 (22) Ex Input Uo, Vt 17.4 V Io, It 18.4 mA Po 80 mW Lo/Ro 445 µH/Ω Ui 10 V Ii 30 mA Ci 15 nF Li 1.
Appendix B. Installation Drawings ACT20X-HTI-SAO (Temperature/mA Converter) Group C o, C a Lo, La IIC or Group A, B 0.3 µF 80 mH IIB or Group C, E, F 1.6 µF 250 mH IIA or Group D, G 8 µF 600 mH Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver) Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver) ATEX Installation Drawing The module is available in the following variants: Order No.
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver) CBX200 – "WI-Manager" Software For installation in Zone 2 / Division 2 the following must be observed: - The CBX200 is an interface cable for configuration via PC. - Configuration must be performed only in a safe area.
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver) Illustration 7-33: ATEX Installation Drawing, (451478 Sheet 1-2) Terminal CH1 (41, 42) and CH2 (43, 44) Input Voltage max 28 V DC Trigger: NPN Low < 2 V, High > 4 V Trigger: PNP Low < 8 V, High > 10 V Terminal (11–12, 21–22) Ex Output ACT20X-SDI-HDO-L ACT20X-2SDI-2HDO Group Co Lo Lo/Ro Uo 28 V IIC 80 nF 4.2 mH 54 µH/Ω Io 93 mA IIB 640 nF 16.8 mH 218 µH/Ω Po 0.65 W IIA 2.1 µF 32.6 mH 436 µH/Ω I 3.
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver) Terminal (11–13, 21–23) Ex Output ACT20X-SDI-HDO-L ACT20X-2SDI-2HDO Group Co Lo Lo/Ro Uo 28 V IIC 80 nF 3.5 mH 50 µH/Ω Io 100 mA IIB 640 nF 14.2 mH 201 µH/Ω Po 0.70 W IIA 2.1 µF 27.6 mH 402 µH/Ω I 3.76 µF 46 mH 667 µH/Ω Ex Output ACT20X-SDI-HDO-L ACT20X-2SDI-2HDO Group Co Lo Lo/Ro Uo 28 V IIC 80 nF 2.9 mH 46 µH/Ω Io 110 mA IIB 640 nF 11.8 mH 184 µH/Ω Po 0.77 W IIA 2.1 µF 22.
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver) Terminal (11–14) Ex Output ACT20X-SDI-HDO-H Group Co Lo Lo/Ro Uo 28 V IIC 80 nF – – Io 135 mA IIB 640 nF 7.8 mH 150 µH/Ω Po 0.95 W IIA 2.1 µF 15.1 mH 301 µH/Ω I 3.76 µF 24 mH 493 µH/Ω Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Input Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Power max 3.
Appendix C.
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver) IECEx Installation Drawing The module is available in the following variants: Order No.
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver) CBX200 – "WI-Manager" Software For installation in Zone 2 / Division 2 the following must be observed: - The CBX200 is an interface cable for configuration via PC. - Configuration must be performed only in a safe area. IECEx Certificate KEM 09.
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver) Illustration 7-34: IECEx Installation Drawing, (451478 Sheet 3-4) Terminal CH1 (41, 42) and CH2 (43, 44) Input Voltage max 28 V DC Trigger: NPN Low < 2 V, High > 4 V Trigger: PNP Low < 8 V, High > 10 V Terminal (11–12, 21–22) Ex Output ACT20X-SDI-HDO-L ACT20X-2SDI-2HDO Group Co Lo Lo/Ro Uo 28 V IIC 80 nF 4.2 mH 54 µH/Ω Io 93 mA IIB 640 nF 16.8 mH 218 µH/Ω Po 0.65 W IIA 2.1 µF 32.6 mH 436 µH/Ω I 3.
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver) Terminal (11–13, 21–23) Ex Output ACT20X-SDI-HDO-L ACT20X-2SDI-2HDO Group Co Lo Lo/Ro Uo 28 V IIC 80 nF 3.5 mH 50 µH/Ω Io 100 mA IIB 640 nF 14.2 mH 201 µH/Ω Po 0.70 W IIA 2.1 µF 27.6 mH 402 µH/Ω I 3.76 µF 46 mH 667 µH/Ω Ex Output ACT20X-SDI-HDO-L ACT20X-2SDI-2HDO Group Co Lo Lo/Ro Uo 28 V IIC 80 nF 2.9 mH 46 µH/Ω Io 100 mA IIB 640 nF 12.8 mH 184 µH/Ω Po 0.70 W IIA 2.1 µF 22.
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver) Terminal (11–14) Ex Output ACT20X-SDI-HDO-H Group Co Lo Lo/Ro Uo 28 V IIC – – – Io 135 mA IIB 640 nF 7.8 mH 150 µH/Ω Po 0.95 W IIA 2.1 µF 15.1 mH 301 µH/Ω I 3.76 µF 24 mH 493 µH/Ω Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Input Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Power max 3.
Appendix C.
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver) FM Installation Drawing The module is available in the following variants: Order No.
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver) CBX200 – "WI-Manager" Software For installation in Zone 2 / Division 2 the following must be observed: - The CBX200 is an interface cable for configuration via PC. - Configuration must be performed only in a safe area.
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver) Illustration 7-35: FM Installation Drawing, (451478 Sheet 5-6) Terminal CH1 (41, 42) and CH2 (43, 44) Input Voltage max 28 V DC Trigger: NPN Low < 2 V, High > 4 V Trigger: PNP Low < 8 V, High > 10 V Terminal (11–12, 21–22) Ex Output ACT20X-SDI-HDO-L ACT20X-2SDI-2HDO Group Co Lo Lo/Ro Uo 28 V IIC 80 nF 4.2 mH 54 µH/Ω Io 93 mA IIB 640 nF 16.8 mH 218 µH/Ω Po 0.65 W IIA 2.1 µF 32.
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver) Terminal (11–13, 21–23) Ex Output ACT20X-SDI-HDO-L ACT20X-2SDI-2HDO Group Co Lo Lo/Ro Uo 28 V IIC 80 nF 3.5 mH 50 µH/Ω Io 100 mA IIB 640 nF 14.2 mH 201 µH/Ω Po 0.70 W IIA 2.1 µF 27.6 mH 402 µH/Ω Ex Output ACT20X-SDI-HDO-L ACT20X-2SDI-2HDO Group Co Lo Lo/Ro Uo 28 V IIC 80 nF 2.9 mH 46 µH/Ω Io 100 mA IIB 640 nF 12.8 mH 184 µH/Ω Po 0.70 W IIA 2.1 µF 22.
Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver) Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Input Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Power max 3.5 W Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.
Appendix C.
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter) Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter) ATEX Installation Drawing The module is available in the following variants: Order No.
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter) CBX200 – "WI-Manager" Software For installation in Zone 2 / Division 2 the following must be observed: - The CBX200 is an interface cable for configuration via PC. - Configuration must be performed only in a safe area.
Appendix D.
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter) Terminal (21–24, 22–24) Input Group Co Lo Lo/Ro Uo 28 V IIC 80 nF 4 mH 54 µH/Ω Io 93 mA IIB 640 nF 16 mH 218 µH/Ω Po 0.65 W IIA or I 2.1 µF 32 mH 436 µH/Ω Group Co Lo Lo/Ro Terminal (21–23) Input Uo 28 V IIC 80 nF 1000 mH 4 mH/Ω Io 1.1 mA IIB 640 nF 1000 mH 17 mH/Ω Po 8 mW IIA or I 2.1 µF 1000 mH 35 mH/Ω Group Co Lo Lo/Ro Terminal (21–22) Input Uo 8.
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter) Terminal (43, 44) Relay Output Non Hazardous Location Zone 2 Installation Voltage max. 250 V AC / 30 V DC 32 V AC / 30 V DC Current max. 2 A AC / 2 A DC 2 A AC / 2 A DC Power max. 500 VA / 60 W 64 VA / 60 W Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.
Appendix D.
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter) Terminal (24–22, 22–21) Input Group Co Lo Lo/Ro Uo 28 V IIC 80 nF 4.2 mH 54 µH/Ω Io 93 mA IIB 640 nF 16 mH 218 µH/Ω Po 0.65 W IIA or I 2.1 µF 32 mH 436 µH/Ω Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (43, 44) Relay Output Non Hazardous Location Zone 2 Installation Voltage max.
Appendix D.
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter) Terminal (22–21, 21–22) Input Group Co Lo Lo/Ro Uo 16.6 V IIC 0.4 µF 1000 mH 25 mH/Ω Io 0.2 mA IIB 2.3 µF 1000 mH 100 mH/Ω Po 0.8 mW IIA or I 9.5 µF 1000 mH 200 mH/Ω Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (43, 44) Relay Output Non Hazardous Location Zone 2 Installation Voltage max.
Appendix D.
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter) IECEx Installation Drawing The module is available in the following variants: Order No.
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter) CBX200 – "WI-Manager" Software For installation in Zone 2 / Division 2 the following must be observed: - The CBX200 is an interface cable for configuration via PC. - Configuration must be performed only in a safe area. IECEx Certificate KEM 10.
Appendix D.
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter) Terminal (21–24, 22–24) Input Group Co Lo Lo/Ro Uo 28 V IIC 80 nF 4 mH 54 µH/Ω Io 93 mA IIB 640 nF 16 mH 218 µH/Ω Po 0.65 W IIA or I 2.1 µF 32 mH 436 µH/Ω Group Co Lo Lo/Ro Terminal (21–23) Input Uo 28 V IIC 80 nF 1000 mH 4 mH/Ω Io 1.1 mA IIB 640 nF 1000 mH 17 mH/Ω Po 8 mW IIA or I 2.1 µF 1000 mH 35 mH/Ω Group Co Lo Lo/Ro Terminal (21–22) Input Uo 8.
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter) Terminal (43, 44) Relay Output Non Hazardous Location Zone 2 Installation Voltage max. 250 V AC / 30 V DC 32 V AC / 30 V DC Current max. 2 A AC / 2 A DC 2 A AC / 2 A DC Power max. 500 VA / 60 W 64 VA / 60 W Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.
Appendix D.
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter) Terminal (24–22, 22–21) Input Group Co Lo Lo/Ro Uo 28 V IIC 80 nF 4.2 mH 54 µH/Ω Io 93 mA IIB 640 nF 16 mH 218 µH/Ω Po 0.65 W IIA or I 2.1 µF 32 mH 436 µH/Ω Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (43, 44) Relay Output Non Hazardous Location Zone 2 Installation Voltage max.
Appendix D.
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter) Terminal (22–21, 21–22) Input Group Co Lo Lo/Ro Uo 16.6 V IIC 0.4 µF 1000 mH 25 mH/Ω Io 0.2 mA IIB 2.3 µF 1000 mH 100 mH/Ω Po 0.8 mW IIA or I 9.5 µF 1000 mH 200 mH/Ω Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (43, 44) Relay Output Non Hazardous Location Zone 2 Installation Voltage max.
Appendix D.
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter) FM Installation Drawing The module is available in the following variants: Order No.
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter) CBX200 – "WI-Manager" Software For installation in Zone 2 / Division 2 the following must be observed: - The CBX200 is an interface cable for configuration via PC. - Configuration must be performed only in a safe area.
Appendix D.
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter) Terminal (21–24, 22–24) Input Group Co Lo Lo/Ro Uo, VOC 28 V IIC or A, B 80 nF 4 mH 54 µH/Ω Io, ISC 93 mA IIB or C, E, F 640 nF 16 mH 218 µH/Ω Po 0.65 W IIA or D, G 2.1 µF 32 mH 436 µH/Ω Group Co Lo Lo/Ro Terminal (21–23) Input Uo, VOC 28 V IIC or A, B 80 nF 1000 mH 4 mH/Ω Io, ISC 1.1 mA IIB or C, E, F 640 nF 1000 mH 17 mH/Ω Po 8 mW IIA or D, G 2.
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter) Terminal (43, 44) Relay Output Non Hazardous Location Zone 2 Installation Voltage max. 250 V AC / 30 V DC 32 V AC / 30 V DC Current max. 2 A AC / 2 A DC 2 A AC / 2 A DC Power max. 500 VA / 60 W 64 VA / 60 W Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.
Appendix D.
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter) Terminal (24-22) Input Ui 30 V Ii 120 mA Pi 900 mW Ci 3 nF Li 2 µH Terminal (24–22, 22–21) Input Group Co Lo Lo/Ro Uo 28 V IIC or A, B 80 nF 4 mH 54 µH/Ω Io 93 mA IIB or C, E, F 640 nF 16 mH 218 µH/Ω Po 0.65 W IIA or D, G 2.1 µF 32 mH 436 µH/Ω Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.
Appendix D.
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter) Terminal (21-22) Input Ui, Vmax 30 V Ii, Imax 120 mA Pi 900 mW Ci 3 nF Li 2 µH Terminal (22–21, 21–22) Input Group Co Lo Lo/Ro Uo, VOC 16.6 V IIC or A, B 0.4 µF 1000 mH 25 mH/Ω Io, ISC 0.2 mA IIB or C, E, F 2.3 µF 1000 mH 100 mH/Ω Po 0.8 mW IIA or D, G 9.5 µF 1000 mH 200 mH/Ω Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.
Appendix D.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) ATEX Installation Drawing The module is available in the following variants: Order No.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) CBX200 – "WI-Manager" Software For installation in Zone 2 / Division 2 the following must be observed: - The CBX200 is an interface cable for configuration via PC. - Configuration must be performed only in a safe area.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Illustration 7-45: ATEX Installation Drawing (1), (453449 Sheet 1-4) Terminal CH1 (13, 14), CH2 (23, 24) Ex Input (Loop Current Source) Uo 28 V Io 93 mA Po 0.65 W Group Co Lo IIC 0.08 µF 3 mH IIB 0.6 µF 12 mH IIA 2.15 µF 25 mH I 3.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Illustration 7-46: ATEX Installation Drawing (2), (453449 Sheet 1-4) Terminal CH1 (11, 12), CH2 (21, 22) Ex Input (External Current Source) Uo 0V Io 0 mA Po 0 mW Ui 30 V Ii 120 mA Pi 0.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Group Co Lo IIC 0.08 µF 3 mH IIB 0.6 µF 12 mH IIA 2.15 µF 25 mH I 3.76 µF 30 mH Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V AC, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Illustration 7-47: ATEX Installation Drawing (3), (453449 Sheet 1-4) Terminal CH1 (14), CH2 (22) Ex Input (Loop Current Source Channel 1 to Channel 2) Uo 28 V Io 93 mA Po 0.65 W Group Co Lo IIC 0.08 µF 3 mH IIB 0.6 µF 12 mH IIA 2.15 µF 25 mH I 3.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Illustration 7-48: ATEX Installation Drawing (4), (453449 Sheet 1-4) Terminal CH1 (12), CH2 (21) Ex Input (External Current Source Channel 1 to Channel 2) Uo 0V Io 0 mA Po 0 mW Ui 30 V Ii 120 mA Pi 0.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Group Co Lo IIC 0.08 µF 3 mH IIB 0.6 µF 12 mH IIA 2.15 µF 25 mH I 3.76 µF 30 mH Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) IECEx Installation Drawing The module is available in the following variants: Order No.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) CBX200 – "WI-Manager" Software For installation in Zone 2 / Division 2 the following must be observed: - The CBX200 is an interface cable for configuration via PC. - Configuration must be performed only in a safe area. IECEx Certificate DEK 11.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Illustration 7-49: IECEx Installation Drawing (1), (453449 Sheet 5-8) Terminal CH1 (13, 14), CH2 (23, 24) Ex Input (Loop Current Source) Uo 28 V Io 93 mA Po 0.65 W Group Co Lo IIC 0.08 µF 3 mH IIB 0.6 µF 12 mH IIA 2.15 µF 25 mH I 3.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Illustration 7-50: IECEx Installation Drawing (2), (453449 Sheet 5-8) Terminal CH1 (11, 12), CH2 (21, 22) Ex Input (External Current Source) Uo 0V Io 0 mA Po 0 mW Ui 30 V Ii 120 mA Pi 0.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Group Co Lo IIC 0.08 µF 3 mH IIB 0.6 µF 12 mH IIA 2.15 µF 25 mH I 3.76 µF 30 mH Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V AC, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Illustration 7-51: IECEx Installation Drawing (3), (453449 Sheet 5-8) Terminal CH1 (14), CH2 (22) Ex Input (Loop Current Source Channel 1 to Channel 2) Uo 28 V Io 93 mA Po 0.65 W Group Co Lo IIC 0.08 µF 3 mH IIB 0.6 µF 12 mH IIA 2.15 µF 25 mH I 3.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Illustration 7-52: IECEx Installation Drawing (4), (453449 Sheet 5-8) Terminal CH1 (12), CH2 (21) Ex Input (External Current Source Channel 1 to Channel 2) Uo 0V Io 0 mA Po 0 mW Ui 30 V Ii 120 mA Pi 0.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Group Co Lo IIC 0.08 µF 3 mH IIB 0.6 µF 12 mH IIA 2.15 µF 25 mH I 3.76 µF 30 mH Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) FM Installation Drawing The module is available in the following variants: Order No.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) CBX200 – "WI-Manager" Software For installation in Zone 2 / Division 2 the following must be observed: - The CBX200 is an interface cable for configuration via PC. - Configuration must be performed only in a safe area.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Illustration 7-53: FM Installation Drawing (1), (453449 Sheet 9-13) Terminal CH1 (13, 14), CH2 (23, 24) Ex Input (Loop Current Source) Uo, VOC 28 V Io, ISC 93 mA Po 0.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Group Co Lo IIC or A, B 0.08 µF 3 mH IIB or C, E, F 0.6 µF 12 mH IIA or D, G 2.15 µF 25 mH Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Illustration 7-54: FM Installation Drawing (2), (453449 Sheet 9-13) Terminal CH1 (11, 12), CH2 (21, 22) Ex Input (External Current Source) Uo, VOC 0V Io, ISC 0 mA Po 0 mW Ui, Vmax 30 V Ii, Imax 120 mA Pi 0.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Group Co Lo IIC or A, B 0.08 µF 3 mH IIB or C, E, F 0.6 µF 12 mH IIA or D, G 2.15 µF 25 mH Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Illustration 7-55: FM Installation Drawing (3), (453449 Sheet 9-13) Terminal CH1 (14), CH2 (22) Ex Input (Loop Current Source Channel 1 to Channel 2) Uo, Voc 28 V Io, Isc 93 mA Po 0.65 W Group Co Lo IIC or A, B 0.08 µF 3 mH IIB or C, E, F 0.6 µF 12 mH IIA or D, G 2.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Illustration 7-56: FM Installation Drawing (4), (453449 Sheet 9-13) Terminal CH1 (12), CH2 (21) Ex Input (External Current Source Channel 1 to Channel 2) Uo 0V Io 0 mA Po 0 mW Ui, Vmax 30 V Ii, Imax 120 mA Pi 0.
Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater) Group Co Lo IIC or A, B 0.08 µF 3 mH IIB or C, E, F 0.6 µF 12 mH IIA or D, G 2.15 µF 25 mH Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Output Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver) Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver) ATEX Installation Drawing The module is available in the following variants: Order No.
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver) CBX200 – "WI-Manager" Software For installation in Zone 2 / Division 2 the following must be observed: - The CBX200 is an interface cable for configuration via PC. - Configuration must be performed only in a safe area.
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver) Illustration 7-57: ATEX Installation Drawing, (453448 Sheet 1-2) Terminal CH1 (11, 12), CH2 (21, 22) Ex Output Uo 28 V Io 93 mA Po 0.65 W Group Co Lo IIC 0.08 µF 4 mH IIB 0.65 µF 16 mH IIA 2.15 µF 32 mH I 3.
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver) Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Current Input Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver) IECEx Installation Drawing The module is available in the following variants: Order No.
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver) CBX200 – "WI-Manager" Software For installation in Zone 2 / Division 2 the following must be observed: - The CBX200 is an interface cable for configuration via PC. - Configuration must be performed only in a safe area. IECEx Certificate DEK 11.
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver) Illustration 7-58: IECEx Installation Drawing, (453448 Sheet 3-4) Terminal CH1 (11, 12), CH2 (21, 22) Ex Output Uo 28 V Io 93 mA Po 0.65 W Group Co Lo IIC 0.08 µF 4 mH IIB 0.65 µF 16 mH IIA 2.15 µF 32 mH I 3.
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver) Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Current Input Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver) FM Installation Drawing The module is available in the following variants: Order No.
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver) CBX200 – "WI-Manager" Software For installation in Zone 2 / Division 2 the following must be observed: - The CBX200 is an interface cable for configuration via PC. - Configuration must be performed only in a safe area. c-FM-us Certificate 3038275 Marking Install in CL I DIV2 GP A-D T4 Provides IS Circuits to CL I-III DIV 1/2 GP A-G or CL I Zn2 AEx/Ex nA nC [ia] IIC T4 Standards Canada Zones: CAN/CSA-C22.
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver) Illustration 7-59: FM Installation Drawing, (453448 Sheet 5-6) Terminal CH1 (11, 12), CH2 (21, 22) Ex Output Uo 28 V Io 93 mA Po 0.65 W Group Co Lo IIC 0.08 µF 4 mH IIB 0.65 µF 16 mH IIA 2.
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver) Terminal (41, 42, 43, 44) and (51, 52, 53, 54) Supply / Current Input Um 253 V, max. 400 Hz Terminal (51, 52) Supply Voltage 19.2…31.2 V DC Terminal (53, 54) Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC Power max. 62.
Appendix G. Installation Drawings ACT20-FEED-IN-PRO (Power Feed-In Unit) Appendix G. Installation Drawings ACT20-FEED-IN-PRO (Power Feed-In Unit) ATEX Installation Drawing The module is available in the following variants: Order No.
Appendix G. Installation Drawings ACT20-FEED-IN-PRO (Power Feed-In Unit) Illustration 7-60: ATEX Installation Drawing, (452691 Sheet 1-2) Terminal (51, 52) Supply Voltage 21.6…26.6 V DC Current 4 A DC Terminal (53, 54) Backup Supply Voltage 21.6…26.6 V DC Current 4 A DC Terminal (41, 42, 43) Power Rail Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 250 V AC / 30 V DC 32 V AC / 30 V DC Current max. 2 A AC / 2 A DC 2 A AC / 2 A DC Power max.
Appendix G. Installation Drawings ACT20-FEED-IN-PRO (Power Feed-In Unit) ACT20-FEED-IN-PRO Power unit with backup. ACT20-FEED-IN-PRO shall only be used with the CH20M-BUS supplied by Weidmüller. Use CH20M BUS-AP (Bus End Plate) to prevent the mounting rail from being short circuited by the outer enclosure. Use CH20M BUS-ADP (Bus Cover) to prevent the open mounting rail from being accidentally short circuited. Redundant ACT20-FEED-IN-PRO Power unit with backup.
Appendix G.
Appendix G. Installation Drawings ACT20-FEED-IN-PRO (Power Feed-In Unit) IECEx Installation Drawing The module is available in the following variants: Order No.
Appendix G. Installation Drawings ACT20-FEED-IN-PRO (Power Feed-In Unit) Illustration 7-61: IECEx Installation Drawing, (452691 Sheet 3-4) Terminal (51, 52) Supply Voltage 21.6…26.6 V DC Current 4 A DC Terminal (53, 54) Backup Supply Voltage 21.6…26.6 V DC Current 4 A DC Terminal (41, 42, 43) Power Rail Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 250 V AC / 30 V DC 32 V AC / 30 V DC Current max. 2 A AC / 2 A DC 2 A AC / 2 A DC Power max.
Appendix G. Installation Drawings ACT20-FEED-IN-PRO (Power Feed-In Unit) ACT20-FEED-IN-PRO Power unit with backup. ACT20-FEED-IN-PRO shall only be used with the CH20M-BUS supplied by Weidmüller. Use CH20M BUS-AP (Bus End Plate) to prevent the mounting rail from being short circuited by the outer enclosure. Use CH20M BUS-ADP (Bus Cover) to prevent the open mounting rail from being accidentally short circuited. Redundant ACT20-FEED-IN-PRO Power unit with backup.
Appendix G.
Appendix G. Installation Drawings ACT20-FEED-IN-PRO (Power Feed-In Unit) FM Installation Drawing The module is available in the following variants: Order No. Installation Drawing Type 8965500000 2456870000 4 52691 Sheet 5-6 ACT20-FEED-IN-PRO-S ACT20-FEED-IN-PRO-P DANGER For safe installation of ACT20-FEED-IN-PRO the following must be observed: The module may only be installed by qualified personnel familiar with the national and international laws, directives and standards that apply to this region.
Appendix G. Installation Drawings ACT20-FEED-IN-PRO (Power Feed-In Unit) Illustration 7-62: FM Installation Drawing, (452691 Sheet 5-6) Terminal (51, 52) Supply Voltage 21.6…26.6 V DC Current 4 A DC Terminal (53, 54) Backup Supply Voltage 21.6…26.6 V DC Current 4 A DC Terminal (41, 42, 43) Power Rail Status Relay Non Hazardous Location Zone 2 Installation Voltage max. 250 V AC / 30 V DC 32 V AC / 30 V DC Current max. 2 A AC / 2 A DC 2 A AC / 2 A DC Power max.
Appendix G. Installation Drawings ACT20-FEED-IN-PRO (Power Feed-In Unit) ACT20-FEED-IN-PRO Power unit with backup. ACT20-FEED-IN-PRO shall only be used with the CH20M-BUS supplied by Weidmüller. Use CH20M BUS-AP (Bus End Plate) to prevent the mounting rail from being short circuited by the outer enclosure. Use CH20M BUS-ADP (Bus Cover) to prevent the open mounting rail from being accidentally short circuited. Redundant ACT20-FEED-IN-PRO Power unit with backup.
Appendix G.