User Documentation

Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)
1066540000/08/12-2018 119
Terminal (1114)
Ex Output
ACT20X-SDI-HDO-H
Group C
o
L
o
L
o
/R
o
U
o
28 V IIC
I
o
135 mA IIB 640 nF 7.8 mH 150 µH/Ω
P
o
0.95 W IIA 2.1 µF 15.1 mH 301 µH/Ω
I 3.76 µF 24 mH 493 µH/Ω
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Input
U
m
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage 19.231.2 V DC
Power max 3.5 W
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC
Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC
Power max. 62.5 VA / 32 W 16 VA / 32 W