User Documentation

Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
34 1066540000/08/12-2018
Illustration 7-6: Applications
RTD Input
Pt100, according to -200…+850 °C, IEC 60751
Ni100, according to -60…+250 °C, DIN 43760
Sensor types
(* = without short circuit detection)
Pt10*, Pt20*, Pt50*, Pt100, Pt250, Pt300, Pt400,
Pt500, Pt1000, Ni50, Ni100, Ni120, Ni1000
Cable resistance per wire (max.) 50 Ω
Sensor current nom. 0.2 mA
Effect of sensor cable resistance (3/4-wire) < 0.002 Ω
Sensor error detection (programmable) ON/OFF
Sensor error current:
when detecting
else
< 2 μA
0 μA