Description
Solenoid / Alarm driver, Type ACT20X-SDI-HDO-L-S, Type ACT20X-SDI-HDO-L-P,
Type ACT20X-SDI-HDO-H-S, Type ACT20X-SDI-HDO-H-P and Type ACT20X-2SDI-2HDO-S,
Type ACT20X-2SDI-2HDO-P, for rail mounting, are 24 V powered isolating barriers, converting
digital signals from PLC's and other equipment into signals for driving valves, solenoids and light
emitting diodes located in a hazardous area.
Ambient temperature range -20 °C to +60 °C.
Marking
The equipment marking may additionally include the code II 3 G Ex nA nC IIC T4 Gc.
Electrical data
Supply (terminals 51, 52): U = 19,2 ... 31,2 Vdc.
Digital input (terminals 41, 42 and 43, 44): U ≤ 60 Vdc
Status Relay (terminals 53, 54):
U ≤ 32 Vdc or 32 Vac, I ≤ 1 Adc or I ≤ 0,5 Aac respectively.
If the Solenoid / Alarm driver is installed outside the hazardous area, the following data for the
relay contacts apply: U ≤ 110 Vdc or 125 Vac, I ≤ 0,3 Adc or I ≤ 0,5 Aac respectively.
For all circuits above: U
m
= 253 Vac (max. frequency 400 Hz).
Solenoid / Alarm driver, Type ACT20X-SDI-HDO-L-S, Type ACT20X-SDI-HDO-L-P and Type
ACT20X-2SDI-2HDO-S, Type ACT20X-2SDI-2HDO-P, output circuits (terminals 11 ... 14 and 21
... 24):
in type of protection intrinsic safety Ex ia IIC/IIB/IIA/IIIC/I, with following maximum values:
U
o
= 28 V; C
o
= 80 nF (IIC) or 640 nF (IIB) or 2,1 µF (IIA) or 3,76 µF (I);
and for terminals 11, 12 and 21, 22:
I
o
= 93 mA; P
o
= 0,65 W; L
o
= 4,2 mH (IIC) or 16,8 mH (IIB) or 32,6 mH (IIA) or 47 mH (I);
L
o
/R
o
= 54 µH/Ω (IIC) or 218 µH/Ω (IIB) or 436 µH/Ω (IIA) or 717 µH/Ω (I);
and for terminals 11, 13 and 21, 23:
I
o
= 100 mA; P
o
= 0,70 W; L
o
= 3,5 mH (IIC) or 14,2 mH (IIB) or 27,6 mH (IIA) or 46 mH (I);
L
o
/R
o
= 50 µH/Ω (IIC) or 201 µH/Ω (IIB) or 402 µH/Ω (IIA) or 667 µH/Ω (I);
and for terminals 11 ... 14 and 21 ... 24:
I
o
= 110 mA; P
o
= 0,77 W; L
o
= 2,9 mH (IIC) or 11,8 mH (IIB) or 22,8 mH (IIA) or 38 mH (I);
L
o
/R
o
= 46 µH/Ω (IIC) or 184 µH/Ω (IIB) or 369 µH/Ω (IIA) or 607 µH/Ω (I).
For group IIIC, the parameters of group IIB apply.
Solenoid / Alarm driver, Type ACT20X-SDI-HDO-H-S, Type ACT20X-SDI-HDO-H-P, output
circuits (terminals 11 ... 14):
in type of protection intrinsic safety Ex ia IIC/IIB/IIA/IIIC/I, with following maximum values:
U
o
= 28 V; C
o
= 80 nF (IIC) or 640 nF (IIB) or 2,1 µF (IIA) or 3,76 µF (I);