User Documentation

Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
1066530000/08/12-2018 133
Terminal (2422, 2221)
Input Group C
o
L
o
L
o
/R
o
U
o
28 V IIC 80 nF 4.2 mH 54 µH/Ω
I
o
93 mA IIB 640 nF 16 mH 218 µH/Ω
P
o
0.65 W IIA or I 2.1 µF 32 mH 436 µH/Ω
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
U
m
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage 19.231.2 V DC
Terminal (43, 44)
Relay Output
Non Hazardous
Location
Zone 2 Installation
Voltage max. 250 V AC / 30 V DC 32 V AC / 30 V DC
Current max. 2 A AC / 2 A DC 2 A AC / 2 A DC
Power max. 500 VA / 60 W 64 VA / 60 W
Terminal (53, 54)
Status Relay Non Hazardous
Location
Zone 2 Installation
Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC
Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC
Power max. 62.5 VA / 32 W 16 VA / 32 W