Appendix G. Installation Drawings ACT20-FEED-IN-PRO (Power Feed-In Unit)
1066530000/08/12-2018 207
FM Installation Drawing
The module is available in the following variants:
Order No. Installation Drawing Type
8965500000
2456870000
4 52691 Sheet 5-6
ACT20-FEED-IN-PRO-S
ACT20-FEED-IN-PRO-P
DANGER
For safe installation of ACT20-FEED-IN-PRO the following must be observed: The module may
only be installed by qualified personnel familiar with the national and international laws,
directives and standards that apply to this region.
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
DANGER
Do not install or remove modules from the Power Rail unless area is known to be non-
hazardous.
WARNING
Substitution of components may impair intrinsic safety and/or suitability for Division 2 / Zone 2.
The installation and wiring must be in accordance with the Canadian Electrical Code for Canada and
National Electrical Code NFPA 70, Article 500 or 505 for installation in USA.
The module must be installed in pollution degree 2 or better.
The module must be supplied from a Power Supply having double or reinforced insulation.
The use of stranded wires is not permitted for mains wiring except when wires are fitted with cable ends.
For installation in Zone 2 or Division 2, the module must be installed in a suitable outer enclosure
according to the regulations in the CEC for Canada or NEC for USA.
The year of manufacture can be taken from the first two digits in the serial number.
c-FM-us Certificate 3043148
Marking
CL I DIV2 GP A-D T4
CL I Zn2 AEx/Ex nA nC IIC T4
Standards Class 3600, Class 3611, Class 3810, ANSI/ISA 12.00.01, ANSI/ISA
12.12.02, ISA 60079-15:2002, CSA-E79-15, CSA-C22.2-213