Approval/Certificate/Document of Conformity

Certificate / Certificat / Zertifikat /
HART transparent
driver
ACT20X-(2)SAI-(2)HAO-S/P
Weidmüller Interface
GmbH CO KG
Detmold, Germany
Systematic Integrity: SC 2 (SIL 2 Capable)
Random Integrity: SIL 2 Capable
Systematic Capability :
The product has met manufacturer design process requirements of Safety
Integrity Level (SIL) 2. These are intended to achieve sufficient integrity against
systematic errors of design by the manufacturer.
A Safety Instrumented Function (SIF) designed with these products must not
be used at a SIL level higher than the statement without “prior use” justification by
end user or diverse technology redundancy in the design.
Random Capability:
The SIL limit imposed by the Architectural Constraints must be met for each
subsystem.
Summary for the HART transparent driver ACT20X-(2)SAI-(2)HAO-S/P:
Configuration:
C1: Single active input and active output
Page 2 of 2
All failure rates are given in FIT=10
-9
/h
SIL Verification:
The Safety Integrity Level (SIL) of an entire Safety Instrumented Function (SIF)
must be verified via a calculation of PFD
AVG
considering redundant architectures,
proof test interval, proof test effectiveness, any automatic diagnostics, average
repair time and the specific failure rates of all products included in the SIF. Each
subsystem must be checked to assure compliance with minimum hardware fault
tolerance (HFT) requirements.
The following documents are mandatory parts of this certificate:
0709-02-C R017 V2 R1 Assessment Report
Safety manual ACT20X-(2)SAI-(2)HAO-S V0.1
l
Safe
l
DD
l
DU
l
Total
SFF DCD MTBF
C1 164 127 48 339 85% 72% 135 y
Type A device
IEC 61508:2000 Failure rates
80 N Main St
Sellersville, PA 18960
T-061, V3R1