User Documentation

Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator)
28 1066540000/08/12-2018
Status Relay Safe Area Zone 2 Installation
Voltage max. 125 V AC / 110 V 32 V AC / 32 V DC
Current max. 0.5 A AC / 0.3 A 0.5 A AC / 1 A DC
Power max. 62.5 VA / 32 W 16 VA / 32 W
Relay Output Safe Area Zone 2 Installation
Voltage max. 250 V AC / 30 V 32 V AC / 30 V DC
Current max. 2 A AC / 2 A DC 2 A AC / 2 A DC
Power max. 500 VA / 60 W 16 VA / 60 W
Max. switching frequency 20 Hz
Opto NPN Output
Max. switching frequency 5 kHz
Min. pulse length 60 μs
Max. load, current / voltage 80 mA / 30 V DC
Voltage drop at 80 mA < 2.5 V DC
Power Supply
Supply voltage 19.2…31.2 V DC
NAMUR supply 8 V DC / 8 mA
Max. consumption (2-channels) 3 W
Fuse 400 mA / 250 V AC
Isolation Voltages (reinforced insulation), Test/Operation
Inputs / outputs / supply 2.6 kV AC / 300 V AC
Output 1 to output 2 1.5 kV AC / 150 V AC
Status relay to supply 1.5 kV AC / 150 V AC
Environmental Specifications
Specifications range -20…+60 °C
Storage temperature -20…+85 °C
Relative humidity (non-condensation) < 95 %
Calibration temperature +20…28 °C