User Documentation
Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)
1066540000/08/12-2018 35
TC Input, Sensor Types Temperature Range Standard
B 0…+1820 °C IEC 60584-1
E -100…+1000 °C IEC 60584-1
J -100…+1200 °C IEC 60584-1
K -180…+1372 °C IEC 60584-1
L -200…+900 °C DIN 43710
N -180…+1300 °C IEC 60584-1
R -50…+1760 °C IEC 60584-1
S -50…+1760 °C IEC 60584-1
T -200…+400 °C IEC 60584-1
U -200…+600 °C DIN 43710
W3 0…+2300 °C ASTM E988-90
W5 0…+2300 °C ASTM E988-90
LR -200…+800 °C GOST 3044-84
Accuracy, General Values Accuracy Temperature Coefficient
All ≤ ±0.1 % of span ≤ ±0.01 % of span / °C
Accuracy, Basic Values Absolute Accuracy Temperature Coefficient
mA ≤ ±16 μA ≤ ±1.6 μA / °C
Pt100, Pt200, Pt1000 ≤ ±0.2 °C ≤ ±0.02 C / °C
Pt500, Ni100, Ni120, Ni1000 ≤ ±0.3 °C ≤ ±0.03 C / °C
Pt50, Pt400, Ni50 ≤ ±0.4 °C ≤ ±0.04 C / °C
Pt250, Pt300 ≤ ±0.6 °C ≤ ±0.06 C / °C
Pt20 ≤ ±0.8 °C ≤ ±0.08 C / °C
Pt10 ≤ ±1.4 °C ≤ ±0.14 C / °C
TC type: E, J, K, L, N, T, U ≤ ±1 °C ≤ ±0.1 C / °C
TC type: R, S, W3, W5, LR ≤ ±2 °C ≤ ±0.2 C / °C
TC type: B (160…400 °C) ≤ ±4.5 °C ≤ ±0.45 C / °C
TC type: B (400…1820 °C) ≤ ±2 °C ≤ ±0.2 C / °C