User Documentation

Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver)
1066540000/08/12-2018 43
Illustration 7-9: Applications
NPN Input (NPN and mechanical switch)
Trigger level (low) 2 V DC
Trigger level (high) 4 V DC
Max. external voltage 28 V DC
Input impedance 3.5
PNP Input
Trigger level (low) 8 V DC
Trigger level (high) 10 V DC
Max. external voltage 28 V DC
Input impedance 3.5