Output
Output ripple < 40 mV RMS
ACT20X-SDI-HDO-L, ACT20X-2SDI-HDO,
low current (< 35 mA),
Ex barrier data channel 1
V
out
no load V
out
with load I
out
max.
1112 min. 24 V min. 12.5 V 35 mA
1113 min. 24 V min. 13.5 V 35 mA
1114 min. 24 V min. 14.5 V 35 mA
ACT20X-2SDI-HDO,
low current (< 35 mA),
Ex barrier data channel 2
V
out
no load V
out
with load I
out
max.
2122 min. 24 V min. 12.5 V 35 mA
2123 min. 24 V min. 13.5 V 35 mA
2124 min. 24 V min. 14.5 V 35 mA
ACT20X-SDI-HDO-H,
high current (< 60 mA),
Ex barrier data channel 1
V
out
no load V
out
with load I
out
max.
1112 min. 24 V
min. 9 V 60 mA
min. 11.5 V 50 mA
1113 min. 24 V
min. 10 V 60 mA
min. 12.5 V 50 mA
1114 min. 24 V
min. 11 V 60 mA
min. 13.5 V 50 mA
Status Relay Safe area Zone 2 Installation
Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC
Current max. 0.5 A AC / 0.3 A DC 0.5 AC / 0.1 A DC
Power max. 62.5 VA / 32 W 16 VA / 32 W