User Documentation

Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver)
1066540000/08/12-2018 45
Power Supply
Supply voltage 19.2…31.2 V DC
Max. consumption (2-channels) 3.5 W
Fuse 1.25 A / 250 V AC
EMC immunity influence < ±0.5 % of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst
< ±1 % of span
Isolation Voltages (reinforced insulation), Test/Operation
Inputs / outputs / supply 2.6 kV AC / 300 V AC
Output 1 to output 2 1.5 kV AC / 150 V AC
Status relay to supply 1.5 kV AC / 150 V AC
Environmental Specifications
Ambient temperature -20…+60 °C
Storage temperature -20…+85 °C
Relative humidity (non-condensation) < 95 %
Calibration temperature +20…28 °C
General Specifications
Communications interface,
adapter / configuration software / FDT-DTM
device driver
CBX200 USB / "WI-Manager" / ACT20X DTM
Dimensions (H x W x D) 105.6 x 22.5 x 114.7 mm
Protection degree IP20
Screw terminal torque 0.5 Nm
Wire size, stranded wire AWG 26…14 / 0.13…2.08 mm²
Default Settings
Channel 1 function Direct
Channel 2 function Direct