User Documentation

Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver)
68 1066540000/08/12-2018
Accuracy Absolute Accuracy Temperature Coefficient
General values ±0.1 % of span ±0.01 % of span / °C
Basic values ±16 µA ±1.6 µA / °C
Status Relay Safe Area Zone 2 Installation
Voltage max. 125 V AC / 110 V 32 V AC / 32 V DC
Current max. 0.5 A AC / 0.3 A 0.5 A AC / 1 A DC
Power max. 62.5 V AC / 32 W 16 VA / 32 W
Power Supply
Supply voltage 19.2…31.2 V DC
Max. consumption (2-channels) 3.5 W
Fuse 1.25 A / 250 V AC
Isolation Voltages (reinforced insulation), Test/Operation
Inputs / outputs / supply 2.6 kV AC / 300 V AC
Input 1 to input 2 1.5 kV AC / 150 V AC
Status relay to supply 1.5 kV AC / 150 V AC
Environmental Specifications
Ambient temperature -20…+60 °C
Storage temperature -20…+85 °C
Relative humidity (non-condensation) < 95 %
Calibration temperature +20…28 °C
General Specifications
Communications interface,
adapter / configuration software / FDT-DTM
device driver
CBX200 USB / "WI-Manager" / ACT20X DTM
Dimensions (H x W x D) 105.6 x 22.5 x 114.7 mm
Protection degree IP20
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6, test Fc, 1g, 2…100 Hz
Vibration, continuous IEC 60068-2-64, test Fh, 1g, 3…100 Hz
Wire size, stranded wire AWG 26…14 / 0.13…2.08 mm²