Brochure/Catalogue

C
C.172729490000
Solenoid driver
Valve control component for control of intrinsically safe
valves, LEDs, acoustic alarms, etc.
PC configuration with FDT/DTM software, download at
www.weidmueller.com
Output current is limited to 35 mA for ignition group IIC
1 or 2 channels in one module
Relay output for error alarm
Technical data
Input
Type
Input voltage
Input resistance, voltage
Ex-output
Type
Output current
Output values
Alarm output
Type
Nominal switching voltage
Continuous current
Power rating
General data
Voltage supply
Power consumption
Tightening torque, min. / Tightening torque, max.
Ambient temperature / Storage temperature
Approvals
Approvals
Insulation coordination
Insulation voltage
Rated voltage
EMC standards
Dimensions
Clamping range (nominal / min. / max.) mm²
Length x width x height mm
Note
Ordering data
1-channel version
Screw connection
PUSH IN connection
2-channel version
Screw connection
PUSH IN connection
Note
ACT20X-SDI-HDO / 2SDI-2HDO
OUT
DC Supply
IN
Ex Safe
to field to I/O (PLC)
max. 35 mA
NPN, PNP transistor, switching signal [input safe-side valve component]
≤ 28 V DC, Trigger level low: ≤ 2.0 V DC (NPN), ≤ 8.0 V DC (PNP),
Trigger level high: ≥ 4.0 V DC (NPN), ≥ 10.0 V DC (PNP)
3.5 kΩ
intrinsically safe circuit, digital, output = input, direct or inverse
(configurable)
max. 35 mA
depending on terminal assignment
Relay, 1 NC (voltage-free)
≤ 125 V AC / 110 V DC (safe area)
≤ 32 V AC / 32 V DC (zone 2)
≤ 0.5 A AC / 0.3 A DC (safe zone), ≤ 0,5 A AC / 1 A DC (zone 2)
≤ 62.5 VA / 32 W (safe area)
≤ 16 VA / 32 W (Zone 2)
19.2…31.2 V DC
≤ 1.9 W
0.4 Nm / 0.6 Nm
-20 °C...60 °C / -20 °C...85 °C
cULus; DETNORVER; DNVGL; EAC; FMEX; FUSAFETY; IECEXKEM;
KEMAATEX
2.6 kV (input / output)
300 V
DIN EN 61326, NE 21
Screw connection PUSH IN
2.5 / 0.25 / 2.5
22.5 / 119.2 22.5 / 127.1
Type Qty. Order No.
ACT20X-SDI-HDO-L-S 1 8965400000
ACT20X-SDI-HDO-L-P 1 2456110000
ACT20X-2SDI-2HDO-S 1 8965420000
ACT20X-2SDI-2HDO-P 1 2456130000
CBX200 USB configuration adapter - 8978580000
Intrinsically safe signal converters – ACT20X
Digital output