Brochure/Catalogue

D
D.12 2729490000
Passive isolators output loop powered
Removable terminals
Power supply via the output circuit (output loop
powered)
2-way isolation
Technical data
Input
Number of inputs
Input voltage
Input current
Output
Load impedance current
Output current
Number of outputs
General data
Accuracy
Configuration
Step response time
Temperature coefficient
Voltage supply
Insulation coordination
EMC standards
Galvanic isolation
Impulse withstand voltage
Insulation voltage
Rated voltage
Overvoltage category
Pollution degree
Dimensions
Clamping range (nominal / min. / max.) mm²
Depth / Width / Height mm
Note
Ordering data
Input voltage
0...10 V
0...5 V
Input current
0...20 mA
4...20 mA
Note
ACT20P-CI-CO-OLP
IN
OUT
active
PLC
I
I
1
7760054120: 0…5 V DC;
7760054121: 0...10 V
7760054118: 0...20 mA;
7760054119: 4…20mA
≤ 600 Ω
4...20 mA, loop-powered
1
< 0.1 % of end value
none
≤ 1 ms
≤ 100 ppm/K
via output current loop, min. 12 V DC/ max. 30 V DC
EN 61010-1:2011, UL 61010-1, IEC61000-6-2, IEC 61000-6-4
2-way isolator
4 kV (1.2/50 µs)
2 kV (Input /Output), 1 min, 50 Hz
300 V
III
2
Screw connection
2.5 / 0.5 / 2.5
114 / 12.5 / 117.2
Type Qty. Order No.
ACT20P-VI-CO-OLP-S 1 7760054121
ACT20P-VI1-CO-OLP-S 1 7760054120
ACT20P-CI1-CO-OLP-S 1 7760054118
ACT20P-CI2-CO-OLP-S 1 7760054119
Passive isolators
Signal converters and monitoring
components – ACT20P