Brochure/Catalogue

D
D.172729490000
Universal limit-value monitoring
Universally configurable input for temperature, voltage,
current, potentiometer, resistance
2 independent relay outputs with multiple limit value
functions: window alarm, upper/lower limits, hysteresis,
delay, etc.
Configuration on the device from 7-segment display or
via FDT/DTM software
External power supply DC or AC
Technical data
Input
Number of inputs
Sensor
Temperature input range
Output (digital)
Alarm function
Rated switching current
Number of digital outputs
Type
Max. switching voltage, AC
General data
Accuracy
Configuration
Step response time
Power consumption
Temperature coefficient
Voltage supply
Insulation coordination
Standards
Pollution degree
Ambient temperature (operational)
Dimensions
Clamping range (nominal / min. / max.) mm²
Depth / Width / Height mm
Note
Ordering data
DC supply voltage
Screw connection
PUSH IN connection
AC supply voltage
Screw connection
PUSH IN connection
Note
ACT20P-UI-2RCO-DC-S
9,3RW57'7&
9
J9,
36
9
7[
1
Thermocouples: B, E, J, K, L, N, R, S, T, U, RTD: PT100, PT200,
PT1000, Ni120, Cu10, 2-/3-/4-wire
B: +100…+1820 °C, E: -270…+1000 °C, J: (-210…+1200 °C), K:
-270…+1372 °C, L: +100…+900 °C, N: (-180…+1300 °C), R: -50…
+1768 °C, S: -50…+1768 °C, T: -270…+400 °C, U: -200…+600 °C
configurable, Top and bottom limit values, window range, Alarm delay:
0…99 s, Hysteresis adjustable, auto / manual reset
200mA @ 110Vdc, 6A @ 24Vdc / 240Vac
2
2 CO contacts, normal / inverse adjustment, Switching frequency 20 Hz
240 V
< 0.1 % of measuring range
With FDT/DTM software, or via 7-segment display, push-buttons and
rotary encoder on the device itself
450 ms
≤ 3.5 W
< 0.02 °C of measuring range / °C
9...60 V DC
DIN EN 61010-1
2
-20 °C...70 °C
Screw connection PUSH IN
2.5 / 0.5 / 2.5
113.6 / 22.5 / 119.2 113.6 / 22.5 / 127.1
Type Qty. Order No.
ACT20P-UI-2RCO-DC-S 1 7940045760
ACT20P-UI-2RCO-DC-P 1 2456840000
ACT20P-UI-2RCO-AC-S 1 1238910000
ACT20P-UI-2RCO-AC-P 1 2495690000
Temperature transducers
Signal converters and monitoring
components – ACT20P