User Documentation

Weidmüller Interface GmbH Co. KG; Klingenbergstraße 16, 32758 Detmold-Germany
Essential Health and Safety Requirements:
Concerning ESRs this Schedule verifies compliance with the Annex III of ATEX directive only. By placing the
product on the market, the manufacturer declares compliance with other relevant Directives, and all other
safety related requirements including those of Annex II of this Directive.
For cross connection accessories current rating, resistance across the terminal please refer to the table
under “technical data” above.
Schedule of Limitations:
The DK-series products are suitable for use in enclosures in atmospheres with flammable gases or
combustible dust. For flammable gases these enclosures must satisfy the requirements according to
EN 60079-0 and EN 60079-7. For combustible dust the enclosure must satisfy the requirements according to
EN 60079-0 and EN 60079-31.
The enclosure shall be constructed to block all sun and UV light from affecting the terminal blocks. The
terminal blocks shall be placed inside a suitable certified IP54 enclosure in type of protection “eb” for gas
atmosphere. For dust atmosphere the terminal blocks shall be mounted inside a suitable certified enclosure
(EN60079-31) in type of protection “t”.
Under normal operating conditions the temperature rise of the terminal blocks is maximum 40 K, measured
at the maximum permitted rated current. Due to the above mentioned, the terminal blocks may be used in
apparatus of temperature classes T6..T1 as long as the terminal block ambient temperature range is not
exceeded. No part of terminal block must exceed 85°C under any condition.
Ambient temperature
T6 (- 50°C ... +40 °C)
T5 (- 50°C … +45 °C)
T4 (- 50°C ... +45 °C)
Note:
If smaller cross sections than the rated cross section are used, the belonging lower current has to be laid
down in the IECEx/EC-Type Examination Certificate of the complete apparatus.
Mounting instructions:
Regarding the use of accessories the instructions of the manufacturer must be followed.
If smaller conductor cross sections than the rated conductor cross sections are used, then the corresponding
lower current shall be stated in the Certificate of the complete apparatus.
Unused terminals shall be tighted.
No other wire sizes or types than the ones specified in instructions must be used. The terminal blocks must
either be mounted next to another block of the same type and size or with an end plate.
When using the DK-series products especially with other terminal blocks series or sizes or accessories the
requirements for clearance and creepage distances according to table 1 of EN 60079-7 must be observed.
Regarding the use of covers, cross-connectors and end brackets the instructions of the manufacturer must
be followed.
Version: DK4QV/35; 13426802 Index: 00 Date: 11.2018