Approval/Certificate/Document of Conformity

C e r t i f i c a t e o f
C o n f o r m i t y
Number CoC-2219236-01
Project number 2219236
Page 2 of 3
IEC 61000-4-30 Power Quality functions tested
The following IEC 61000-4-30 measurement methods have been tested
Table 1 IEC 61000-4-30 Power Quality functions tested
IEC 62586-2
Clause
Parameter
IEC 61000-4-30
class
Comments
6.1 / 7.1
Power frequency
A
50 and 60 Hz
6.2 / 7.2
Magnitude of supply voltage
A
230 V and 57,7 V
6.3 / 7.3
Flicker
A
Class F3: 230 V, 60 Hz
120 V, 50 Hz
6.4 / 7.4
Supply voltage interruptions, dips
and swells
A
50 and 60 Hz
6.5 / 7.5
Supply voltage unbalance
A
6.6 / 7.6
Voltage harmonics
A
6.7 / 7.7
Voltage interharmonics
A
6.8 / 7.8
Mains signalling voltages on the
voltage supply
A
Method 2
6.9 / 7.9
Measurement of underdeviation
and overdeviation parameters
A
6.10 / 7.10
Flagging
A
6.11 / 7.11
Clock uncertainty testing
A
6.12 / 7.12
Variation of external influence
quantities
A
Temperature: -10°C ... +55°C
6.13 / 7.13
Rapid Voltage Changes (RVC)
A
6.14 / 7.14
Magnitude of current
A
6.15 / 7.15
Harmonic current
A
6.16 / 7.16
Interharmonic currents
A
6.17 / 7.17
Current unbalance
A
8
Calculation of measurement
uncertainty and operating
uncertainty
A
A : compliance with class A
S : compliance with class S
--- : Not implemented
The tests are performed in accordance with IEC 62586-2 edition 2 (2017).