4.2 Energy Meter 610
4.2.1 Connection to computer
Example 1:
The Energy Meter 610 and the PC have an RS232 interface.
Example 2:
The Energy Meter 610 has an RS485 interface and the PC has an Ethernet interface. A gateway is required.
The following devices can be used as gateways: Energy Analyser D550, Energy Analyser 550.
Example 3:
The Energy Meter 610 has an RS485 interface and the PC has an Ethernet interface. A gateway is required.
The following devices can be used as gateways: Energy Analyser D550, Energy Analyser 550.
4.2.2 Adding device
Integrating Energy Meter 610 in ecoExplorer go
• CreateanewEnergyMeter610inecoExplorergoanddenetheappropriatetypeofconnectionforyour
device (First steps, Adding new device).
Connection types
Ethernet gateway (e.g. for the devices connected to the RS485)
A gateway is required to be able to connect the Energy Meter 610 via Ethernet to the PC and to be able to
congureitandreaditwithecoExplorergo.
• The Energy Meter 610 has an RS485 interface.
• The gateway must have both an RS485 and an Ethernet interface (e.g. a Energy Analyser D550 with the
appropriate options).
• Thegatewayaddress(e.g.192.168.1.1)mustbesetundertheconnectionsettings(seeFig.Conguring
the connection).
• Because more than one Energy Meter 610 can be connected to the gateway, the device address set in
theEnergyMeterD370mustalsobesetundertheconnectionsettings(seeFig.Conguringtheconnec-
tion).
• If no connection could be established to the Energy Meter 610, an attempt will be repeated following the
set Timeout.
• When attempting to read data from the Energy Meter 610, the number of attempted connections will be
limited by the number set under Max. no. of attempts.
• The connection protocol must be set via the Modbus protocol. TCP/IP packets are used when connecting
via Modbus TCP. The TCP port 502 is reserved for Modbus TCP.
• When measuring online, the ecoExplorer go will repeatedly attempt to establish a connection to the En-
ergy Meter 610.
Modbus RTU (RS485/RS232)
• Using an RS485 connection, a direct connection can be established over an interface converter between